Feeder Protection
REF601
Product version: 2.0
17. Protection functions
Table 20. Low-set phase overcurrent protection, stage I> / 51
Parameter
Value (Range)
Setting range of pick-up current ‘I >’
0.2...1.0 x I
n
in steps 0.025, infinite
Operation accuracy
±
5.0% of set value
Operate time delay (DMT) ‘t >’
0.1...1.6 sec in steps of 0.1 for B=1
0.5...8.0 sec in steps of 0.5 for B=5
Operation time accuracy
±
5.0% of set value or
±
30 msec
Operating curve type
Normal inverse, Very inverse, Extremely inverse, Long-time inverse
IEC 60255-3:
Special curves:
RI inverse
Time multiplier setting ‘k’
0.1...1.6, in steps of 0.1
Operation time accuracy
class E(5) or
±
30 msec
±
5.0% of set value or
±
30 msec
IEC characteristics
RI characteristics
Reset ratio
IDMT : 0.96 and DT : 0.98
Table 21. High-set phase overcurrent protection, stage I>> / 50-1
Parameter
Value (Range)
Setting range of pick-up current ‘I >>’
1.0...2.75 x I
n
in steps 0.25, infinite
Operation accuracy
±
5.0% of set value
Operation mode
Definite time
Operation time accuracy
±
5.0% of set value or
±
30 msec
Reset ratio
0.98
Operate time delay (DMT) ‘t >>’
0.1...0.45 sec in steps of 0.05
Table 22. Very High-set phase overcurrent protection, stage I>>> / 50-2
Parameter
Value (Range)
Setting range of pick-up current ‘I >>>’ 2.0...15.0 x I
n
in steps 1.0, infinite
Operation accuracy
±
5.0% of set value
Operation mode
Instantaneous
Operation time accuracy
±
15 msec
Reset ratio
0.98
Operate time ‘t >>>’
0.05 sec