background image

2015 Oventrop

1

Thermal drainage protection device

Tender specification:

Oventrop  thermal  drainage  protection  devices  limit  the  water
temperature  in  boilers  with  integrated  water  heater  or
continuous-flow  water  heater  in  closed  hot  water  heating
systems for different fuels or solid fuels. 

They  comply  with  the  EN  14597  standard  and  can  be  used  in
installations  according  to  EN  12828  regarding  solid  fuel  boilers
with manual fuel supply and capacities of less than 100 kW.

The  installation  of  the  thermal  drainage  protection  device  is
mandatory  in  systems  in  which  the  heat  generator  has  to  be
equipped with a water heater.

Item no.:

                                          1354699

Technical data:

Max. excess operating pressure:     10 bar

Max. operating temperature:            122 °C

Response temperature:                    about 95 °C

Temperature range:                          5 °C - 110 °C

Ambient temperature:                       0 °C - 70 °C

Fluid:                                                 Water

Flow capacity:                                  2.05 m³/h t ∆P 1 bar

Operation mode (EN 14597):            2 KP

PED category:                                   IV

Installation position:                          Any

Length of capillary:                           1.3 m

Connection threads:

- Valve                                               both ports Rp 

3

4

- Immersion pocket                          G 

1

2

Immersion depth below hexagon:    153 mm

Component marking:                        TÜV.TH.797-13

DIN-reg.-no.:                                     TH 797

Function:

The  Oventrop  thermal  drainage  protection  device  is  a  pressure
balanced single-seated valve which opens with the temperature
rising. Control is carried out via two working elements which act
independently of each other.
The thermal drainage protection device can be vented manually. 

The  cold  water  entering  the  potable  water  heater  provokes  an
indirect  cooling  down  of  the  boiler  and  an  exceedance  of  the
max. permissible temperature of 115 °C is avoided. 

Technical information

Dimensions

60

21 mm spanner

R

p

 

3

4

D

IN

 E

N

 1

02

26

-1

R

p

 

3

4

D

IN

 E

N

 1

02

26

-1

Ø

 3

1

22 mm spanner

1

2

Ø 16

3

1

7

0

1

5

3

Thermal drainage protection device

Reviews: