Fig. 6.5.1.1.-1 Protocol Editing Tool with the LonMark POD
Application ID
Application ID is a number defining the source of the application event. When the
application is an IEC 61131 function block, the ID equals the function block ID
number, for example, MEVO3A has the ID number 204. In REC 523, there are also
events coming from the non-IEC 61131 applications. These are the events related to
the battery and heating monitoring. They are presented through the event channel
17. For more details about the channel 17 event profile, see CD-ROM Technical
Descriptions of Functions (refer to Section 1.9. Document revisions).
100
a. The table index 000 illustrates the conversion of the disconnector position process data (CODC1)
into a 16-bit network variable (index 68, two least significant bits). The Event Mask2 for the table
index 000 means that the events E0, E1, E2 and E3 are set.
b. The table index 001 is an example of the conversion of the analogue measurement process data
(MECU3A, phase current 1) into a float type of network variable (index 78). The Event Mask2 for the
table index 000 means that the events E0, E1, E6, E7, E12, E13, E18, E19 and E25 are set.
Table 6.5.1.1-1
POD structure (Continued)
Table
index
Application Id
(channel,
FblockId)
Event Mask1
(E32...E63)
Event Mask2
(E0...E31)
Output Network
variable name
Process data
object name