6.2.
Communication interfaces
The REC 523 offers interface for various type of communication media used in
distribution automation applications. The communication media includes:
• Public telephone lines
• Leased lines
• Digital line carrier (DLC)
• Digital cellular phones (GSM)
• Analogue or digital radio
• Optical cables
• Satellite communication
Fig. 6.2.-1 Radio telephone connection
Table 6.1.-1
9-pin communication port signal layout
A040383
Connector X5.1 F RS 232/
remote protocol
a
a. “F” after connector means female connector and “M” male connector.
Connector X5.2 M RS 232/
SPA parametrization
a
Connector X5.3 F
RS 485/
LON or SPA
a
1
1
1
DATA_A
2
RXD
2
RXD
2
DATA_B
3
TXD
3
TXD
3
RTS_A
4
(do not connect)
4
+15 V
4
RTS_B
5
GND
5
GND
5
LON_COL_A
6
6
DSRB
b
b. When DSRB pin is set to +15 V, SPA bus protocol is in use (9600, even, 7 data bits, 1 stop bits, SPA
bus address 1.
6
LON_COL_B
7
RTS
7
RTS
7
GND
8
CTS
8
8
xLON_Switch
9
9
9
VCC
1
5
6
9
REC 523
X7.1
6
7
Radio_b
RADIO
TELEPHONE
+12 V
GND
TX-LINE >
RX-LINE <
Radio ON
SQUELCH
STATE
X5.1
RS232
Modem