![ABB REC 523 Technical Reference Manual Download Page 41](http://html.mh-extra.com/html/abb/rec-523/rec-523_technical-reference-manual_2767041.webp)
1MRS750881-MUM
REC 523
41
Remote Monitoring and Control Unit
Technical Reference Manual
Nonc2
Fig. 5.5.2.2.-1 Signalling Output (SO)
5.6.
LED panel and LED outputs
The LED panel is fully programmable through the Relay Configuration Tool (for an
example configuration, see Fig. 5.6.-2 ). Each LED has four states: ON, OFF, fast
blinking (2 Hz) and slow blinking (0.5Hz). The value field of each LED global
variable is 16 bit and the consecutive bit pairs (0 and 1, 2 and 3, and so on)
correspond to one LED state. The four states are illustrated in Fig. 5.6.-1 .
At power up, a test is run for the LED panel for its visual inspection. A testing
sequence can also be initiated via the global variable PSC_7_LEDTEST in the Relay
Configuration Tool.
A050013
Fig. 5.6.-1 LED panel and different LED states
NO/NC
NO
e.g.
PSC_7_SO1
e.g.
BIO1_3_SO1
LED 8 state fast blink
LED 1 state on
↓
↓
10
00
11
00
01
00
10
11
00
=Blank led
01
=Fast blink
10
=Slow blink
11
=LED on
ON
I RF
1
2
3
4
5
6
7
8
9
10
11
12 13 14
15
16
17
18
19
20 21 STO