1MRS750500-MUM
Feeder, Machine and Transformer Terminals
Operator’s Manual
RE_ 54_
25
5.4.2.
Setting a parameter
Parameters can be set on the last menu level, the parameter menu. One parameter
consists of 2 rows:
1. row: parameter text
2. row: the setting value
(numeric value, character string, enumerator)
To set a parameter
1. In the parameter menu, press [
↓
]
or [
↑
]
to select a parameter (the cursor moves
two rows at a time)
2. When the appropriate parameter is highlighted, press [E] for 2 seconds
3. Enter the password (see Figure 5.2.-1) and press [E]
(the password is only required for the first parameter setting and will apply as
long as the user stays at technical level or the backlight time-out elapses)
4. Set the parameter
• In case of an enumerator (the entire text is flashing), press [
↓
]
or [
↑
]
to scroll
for the desired item
• In case of a numeric value or a character string (the first digit/character is
flashing):
I Press [
→
] or [
←
] to select a digit/character
II Press [
↓
]
or [
↑
]
to scroll for the desired digit/character
III Repeat I and II to define other digits/characters
5. Press [E] to confirm the new setting or [C] to restore the previous setting
• When a parameter change is confirmed with [E], the new setting takes effect
immediately. However, all parameter changes need to be saved in the non-
volatile memory as described in section “Saving parameters” on page 26.
• If an illegal setting value is confirmed, a message in the assisting window tells
the user that the setting is out of range, and the previous parameter value
remains unchanged.
Note! The special parameters for measuring devices in
MAIN MENU/
Configuration/Current trafo
, ...
/Rogow.sensor
,
...
/Voltage trafo
and ...
/Volt. divider
become valid only
after they have been stored via the parameter “Store” and the terminal has
been reset via the parameter “Software reset” in
MAIN MENU/
Configuration/General
.
Table 5.4.2-1
Parameter setting types
Type
Description
Example
Numeric value
One digit is flashing and can be
changed at a time
“Start current” parameter:
e.g. 001.0 % In
Character string
One character (or digit) is flashing and
can be changed at a time
“Main header” parameter
(MEDREC16 function block):
e.g. Default header
Enumerator
The whole text is flashing:
select one of the predetermined
alternatives
“Operation mode” parameter:
• Not in use
• Definite time
• Instantaneous
!