1MRS750500-MUM
Feeder, Machine and Transformer Terminals
Operator’s Manual
RE_ 54_
19
5.2.
Passwords
The HMI includes three passwords with different uses. By default, passwords 1 and
3 are disabled.
1
The user can take the passwords 1 and 3 in use in
MAIN MENU/Configuration/Password
(
/MIMIC
or
/Level
).
To take a password (1 or 3) in use
1. In the MIMIC view at user level, press [E] for 2 s to access the technical level
2. Press [
↑
] or [
↓
] to select Configuration (last item) in the MAIN MENU
3. Press [
→
] to move to the Configuration menu
4. Press [
↓
] to select Password
5. Press [
→
] to move to the Password menu
6. Press [
↓
] or [
↑
] to select MIMIC (password 1) or Level (password 3)
7. Press [
→
] to move to the selected menu
8. The cursor is at the first parameter, “Activate passw.”, press [E] and enter the
password to activate the setting mode
9. Press [
↓
] to set the parameter to “Activate”
10.Confirm the setting by pressing [E]
11.To disable the other password, press [
←
] to return to the previous menu and
repeat steps 6 to 10.
To take a password out of use, set the parameter “Activate passw.” to “Do not
activate”.
Table 5.2.-1
Passwords
Password Application
Status
Default
Password 1
(MIMIC)
Local/remote/disabled/logic selection with the
[R\L] button
• The password is reset after a preset time-out
(backlight time) and must be re-entered
before using the [R\L] button again.For more
information about the preset time-out, please
refer to section “Display backlight” on page 9.
• The password is reset when entering the
technical level.
Enabled/disabled
(can be taken in use)
100000
Password 2
(parameter)
Entering the parameter setting mode at
technical level
• The password applies as long as the user
stays at technical level or until the backlight
time-out elapses.
Always enabled
200000
Password 3
(HMI level)
Entering the technical level
from MIMIC view to MAIN MENU
Enabled/disabled
(can be taken in use)
300000
1. In terminals prior to Release 3.0, all passwords are enabled by default.