background image

11.

Connection of the communication and control signals

12.

Commissioning

13.

Instruments

PVI-3.0_3.6_4.2-TL-OUTD-Quick Installation Guide EN-RevB

EFFECTIVE 2014-02-25

© Copyright 2014 ABB.  All Rights Reserved.

Specifications subject to change without notice.   

8.

Input connection (DC)

9.

Line cable and protection devices 

 

10.

Output connection (AC)

14.

Structure of the display menu

15.

Characteristics and technical data

Load protection breaker (AC disconnect switch) and line cable sizing

To protect the AC connection line of the inverter, we recommend installing a device for protection against over current and leakage with the following characte-

ristics:

PVI-3.0-TL-OUTD

PVI-3.6-TL-OUTD

PVI-4.2-TL-OUTD

Type

Automatic circuit breaker with differential thermal magnetic protection

Nominal Voltage

230 Vac

Nominal Current

20 A

25 A

Magnetic protection characteristic

B/C

Number of poles

2

Type of differential protection

A/AC

Differential sensitivity

300 mA

ABB declares that the ABB transformerless inverters, in terms of their construction, do not inject continuous ground fault currents and therefore there is no requirement 

that the differential protection installed downstream of the inverter be type B in accordance with IEC 60755 / A 2.

Characteristics and sizing of the line cable

Three-pole cable required. The cross-section of the AC line conductor must be sized in order to prevent unwanted disconnections of the inverter from the grid 

due to high impedance of the line that connects the inverter to the power supply point.

Cross-section of the line conductor (mm

2

)

Maximum length of the line conductor (mt)

PVI-3.0-TL-OUTD

PVI-3.6-TL-OUTD

PVI-4.2-TL-OUTD

4 mm²

19 m

16 m

14 m

6 mm²

29 m

24 m

21 m

10 mm²

48 m

41 m

35 m

16 mm²

77 m

65 m

56 m

The values are calculated in nominal power conditions, taking into account: 

1. a power loss of not more than 1% along the line.    2. copper cable, with HEPR rubber insulation, laid in free air

Contact us

www.abb.com/solarinverters

Check for correct polarity in the input strings and absence of any leakage to ground in the PV 

generator. When exposed to sunlight, the PV panels supply DC direct voltage to the inverter. The 

inside of the inverter may only be accessed after the equipment has been disconnected from the 

grid and from the photovoltaic generator.

Warning! The inverters to which this document relates to are WITHOUT ISOLATION TRANSFOR-

MER (transformer-less). This type involves the use of insulated photovoltaic panels (IEC61730 

Class A Rating) and the need to maintain the photovoltaic generator floating with respect to earth: 

no pole of the generator must be connected to earth.

For the string connections it is necessary to use the quick fit connectors (multicontact or weidmüller) located on the 

bottom of the mechanic 

17

 

18

.

The number of quick fit connectors changes based on the model of inverter.

PVI-3.0-TL-OUTD

PVI-3.6-TL-OUTD

PVI-4.2-TL-OUTD

No. of input channels

2

2

No. of quick fit 

connectors

4 (2 pairs)

4 + 2 (2 pairs per MPPT1 

17

 and 

1 pairs per MPPT2 

18

)

 -

Crimp the Multicontact/Weidmüller MC4/WM4 quick fit connector counterparts (supplied) to the string cables or to 

the cables wired to the DC disconnect switches (external)

 -Connect all the strings included in the design of the system and always check the tightness of the connectors

 -If some of the string inputs should not be used you must proceed to verify the presence of covers on DC input 

connectors and then install them should they be absent: this operation is necessary for the tightness of the inverter 

and to avoid damaging the free connector that could be used at a later date. 

PVI-3.0/3.6-TL-OUTD-S

17

18

PVI-4.2-TL-OUTD-S

17

18

  max 16 mm²

10 ÷ 17 mm

Warning! Before performing any of the operations described below, ensure the AC line downstream 

the inverter has been correctly disconnected

 -

Remove the protective film located on the hole to be used for the AC cables 

19

 -Insert the M25 cable gland in the hole and secure it using the special M25 lock nut (supplied)

Warning! To ensure environmental protection IP65 it is necessary to fix the cable gland to the inverter 

chassis with a minimum tightening torque of 7.5 Nm

 -Strip 10 mm of sheathing from the AC grid connection cables

 -Plug the AC line cable into the inverter, passing it through the previously installed cable gland

 -Connect the protective earth (yellow-green) cable to the contact labelled with the 

 symbol on the terminal block 

10

Warning! ABB inverters should be earthed (PE) via the terminal with the protective earth label  , using a cable with an appropriate cross-

section of the conductor for the maximum ground fault current that the generating system might experience

 -Connect the neutral cable (normally blue) to the terminal labelled with the letter 

N

 -Connect the phase cable to the terminal labelled with the letter 

L

Warning! The AC cables must be tightened on the terminal block with a minimum torque of 1.5 Nm

Once the connection to the terminal board 

10

 is complete, screw in the cable gland firmly (tightening torque 5.0Nm) and check the tightness.

10

Each cable which must be connected to the connectors of the communication and control signals must pass through one of the two service cable glands 

20

.

An M20 cable gland (that takes cables from 7 mm to 13 mm in diameter) and a gasket with two holes to insert into the cable gland which enables two separate 

cables of a maximum diameter of 5 mm to be accommodated, are available.

Warning! To ensure environmental protection IP65 it is necessary to fix the cable glands to the inverter chassis with a minimum tightening 

torque of 7 Nm

Connection to the RS485 communication line

The RS485 communication port is the inverter’s communication port. 

The ABB inverters use an RS485 HALF-DUPLEX communication line 

made up of two transmission and reception cables (+T/R and –T/R) and a 

communication reference cable (RTN): all three cables must be connected 

in daisy-chain configuration. The chain connection can be made without 

distinction by using the RJ45 connector couples 

14

 (one for in and one for 

out) or the terminal block 

13

.The last inverter in the daisy chain must be 

“terminated” or the 120 Ohm communication line termination resistance 

must be activated by switching the dip-switch 

15

.

Using the alarm terminal block

Terminal block 

13

 connecting to the configurable relay that allows con

-

nection of external devices which, according to the mode selected in the 

menu “

SETTINGS > Alarm

” can, for example, signal malfunctions. The 

operating modes that can be set are: Production and Alarm.

14

15

13

The ALARM contact can be used only with systems that ensure a safety isolating additional at least (supplementary insulation in relation 

to the DC input voltage)

Using the REM terminal block

The REM terminal block 

13

, if suitably configured, allows the “Remote ON/OFF” function to be used: this function allows remote disconnection of the inverter 

from the grid

For further information regarding the configuration and use of the communication and control signals terminal block, please see the 

manual

The inverter commissioning procedure is as follows:

 -Switch the integrated switch 

16

 (version –S) to the ON position or close the external switches: If the input voltage applied to one of the two input channels is 

greater than the minimum starting voltage, the inverter will start up.

 -

When the inverter is turned on for the first time you will be asked to select the “Nation” of installation. This selection allows the inverter to automatically confi

-

gure its parameters to ensure that compliance with local standards; the default language corresponding to the selected “Nation” will also be set.

Warning! After the grid standard was set you have 24 hours to make any changes to the grid standard value; 24 hours later the “Nation 

Select.” functionality will be blocked, and any subsequent changes can only be made using a password provided on request by ABB

 -

After you have set the “Nation” value, the message “Inizializing...Please Wait” is displayed. Depending on the input voltage value, the inverter will show 

various messages on the display and change the behaviour of the three LED 

06

:

INPUT VOLTAGE

DISPLAY MESSAGE

LED STATUS

DESCRIPTION

Vin < Vstart

Waiting Sun

Green  = FLASHING

Yellow = OFF

Red      = OFF

The input voltage is not sufficient to permit connection to the grid.

Vin > Vstart

Missing Grid

Green  = FLASHING

Yellow = ON

Red      = OFF

There is sufficient input voltage to permit connection to the grid: 

the inverter waits until there is grid voltage to carry out the parallel 

connection.

The inverter is powered ONLY by the voltage coming from the photovoltaic generator: presence of grid voltage alone IS NOT SUFFICIENT to permit 

the inverter to start up.

 -With the inverter in “Missing Grid” status, close the AC switch downstream the inverter so as to supply the grid voltage to the inverter: the inverter performs 

the grid voltage check, measures the photovoltaic generator insulation resistance against earth and carries out other self-diagnosis checks. During the 

checks before the parallel with the grid, the green LED keeps flashing, the others are off.

During the grid voltage check and measurement of the insulation resistance, the values for the grid voltage and frequency and the insulation resi-

stance measured by the inverter are shown on the display. The inverter completes parallel connection with the grid SOLELY if the grid parameters 

meet the ranges provided for by the regulations in force and if the insulation resistance is greater than 1Mohm.

 -If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. At this 

stage, the display shows the inverter’s parameters in cycles. The green LED stays lit whereas the others are off.

LEDs and BUTTONS

, in various combinations, can be used to view the status or carry out complex actions that are described more fully in the manual.

08

07

06

LED

POWER

GREEN

 On if the inverter is working correctly. Flashes when 

checking the grid or if there is insufficient sunlight.

ESC

It is used to access the main menu, to go back to the previous menu 

or to go back to the previous digit to be edited

LED

ALARM

YELLOW

 The inverter has detected an anomaly. The anomaly 

is shown on the display.

UP

It is used to scroll up the menu options or to shift the numerical scale 

in ascending order

LED

GFI

RED 

Ground fault on the DC side of the PV generator. The 

error is shown on the display.

DOWN

It is used to scroll down the menu options or to shift the numerical 

scale in descending order

ENTER

It can be used to confirm an action, to access the submenu for the 

selected option (indicated by the > symbol) or to switch to the next 

digit to be edited

ABB inverters are equipped with a graphic Display 

07

, consisting of 2 lines of 16 characters each, which can be used to:

 -Display the operating state of the inverter and the statistical data

 -Display the service messages for the operator

 -Display the alarm and fault messages for the operator

 -Changing the settings of the inverter

During the normal operation of the inverter the display cycles through the 

GENERAL INFORMATION

. This information relates to the input and output parame-

ters and the inverter identification parameters. By pressing 

ENTER

 it is possible to lock scrolling on a screen to be constantly displayed.

Press 

ESC

 to access the three main menus, which have the following functions:

 

-

STATISTICS:

 

Displays the statistics

 

-

SETTINGS:

  

Modify the settings of the inverter 

 

-

INFO:

 

 

View service messages for the operator

Refer to the manual for details regarding use and functions available in the menu

PVI-3.0-TL-OUTD

PVI-3.6-TL-OUTD

PVI-4.2-TL-OUTD

Input

Absolute Maximum Input Voltage (V

max,abs

)

600 V

Input Activation Voltage (V

start

)

200 V (adj. 120...350 V)

Input Operating Range (V

dcmin

...V

dcmax

)

0.7 x Vstart...580 V

Rated DC Input Power (P

dcr

)

3120 Wp

3750 Wp

4375 Wp

Number of Independent MPPTs 

2

Maximum Input Power for each MPPT (P

MPPT max

)

2000 W

3000 W

3000 W

MPPT Input DC Voltage Range (V

MPPT min

,f ... V

MPPT max

,f) at P

acr

160...530 V

120...530 V

140...530 V

Maximum DC Input Current (I

dc max

) / for each MPPT (I

MPPT max

)

20.0 A / 10.0 A

32.0 A / 16.0 A

32.0 A / 16.0 A

Maximum Input Short Circuit Current for each MPPT

12.5 A

20.0 A

20.0 A

Maximum Backfeed current (from AC to DC side)

Negligible

Number of DC Inputs Pairs for each MPPT

1

1

2 for MPPT1 and 1 for MPPT2

DC Connection Type

Tool Free PV Connector WM / MC4

Input protection

Reverse Polarity Protection

Yes, from limited current source

Input Overvoltage Protection for each MPPT - Varistor

2

Photovoltaic Array Isolation Control

According to local standard

DC Switch Rating (-S Version)

Max. 25.0 A / 600 V

Output

AC Grid Connection Type

Monophase

Rated AC Power (P

acr

)

3000 W

3600 W

4200 W

Maximum AC Output Power (P

ac max

)

3300 W 

(1)

4000 W 

(2)

4600 W 

(3)

Rated AC Grid Voltage (V

acr

)

230 V

AC Voltage Range

180...264 Vac 

(4)

Maximum AC Output Current (I

ac max

)

14.5 A

17.2 A 

(5)

20.0 A

Inrush Current

Negligible

Maximum Output Fault Current

<25 A rms (100mS)

Rated Output Frequency (f

r

)

50 Hz / 60 Hz

Output Frequency Range (f

min

...f

max

)

47...53 / 57...63 Hz 

(6)

Nominal Power Factor (Cosphi

acr

)

>0.995 adj. ± 0.9 with Pacr= 

3.0 kW

>0.995 adj. ± 0.9 with Pacr= 

3.6 kW

>0.995 adj. ± 0.9 with Pacr= 

4.2 kW

Total Harmonic Distortion of Current 

< 3.5%

AC Connection Type

Screw terminal block

Output protection

Anti-Islanding Protection

According to local standard

Maximum AC Overcurrent Protection

16.0 A

19.0 A

22.0 A

Output Overvoltage Protection - Varistor

2 (L - N / L - PE)

Operating performance

Maximum Efficiency (η

max

)

96.8%

Weighted Efficiency (EURO/CEC)

96% / -

Power Input Treshold

10.0 W

Stand-by Consumption

< 8.0 W

Communication

Wired Local Monitoring

PVI-USB-RS232_485 (opt.), PVI-DESKTOP (opt.)

Remote Monitoring

PVI-AEC-EVO (opt.), VSN700 Data Logger (opt.)

Wireless Local Monitoring

PVI-DESKTOP (opt.) with PVI-RADIOMODULE (opt.)

User Interface

LCD Display with 16 characters x 2 line

Environmental

Ambient Temperature Range

-25...+60°C /-13...140°F with 

derating above 50°C/122°F

-25...+60°C /-13...140°F with 

derating above 55°C/131°F

-25...+60°C /-13...140°F with 

derating above 50°C/122°F

Storage Temperature

-40...80°C (-40...+176°F)

Relative Humidity

0...100% condensing

Environmental pollution classification for external environment

3

Noise Emission

< 50 dB(A) @ 1 m

Maximum Operating Altitude without Derating

2000 m / 6560 ft

Environmental Category

External

Physical

Environmental Protection Rating

IP 65

Cooling

Natural

Dimension (H x W x D)

618 x 325 x 222 mm    /    24.3 x 12.8 x 8.7 inch

Weight

17.5 kg / 38.6 lb

Mounting System

Wall bracket

Overvoltage Category in accordance with IEC 62109-1

II (DC input)    III (AC output)

Safety

Isolation Level

Transformerless (TL)

Safety Class

I

Marking

CE 

(50Hz only)

1. Limited to 3000 W for Germany

2. Limited to 3600 W for Germany

3. Limited to 4200 W for Germany

4. The AC voltage range may vary depending on specific country grid standard

5. Restricted to 16 A (up to the maximum output power of 3680 W) for the 

standard UK G83/1.

6. The Frequency range may vary depending on specific country grid standard

Remark. Features not specifically listed in the present data sheet 

are not included in the product

Reviews: