16 Softstarters Type PSTX30...PSTX570 User Manual short form 1SFC132082M9901
EN
Protections
Parameter name
Setting range
Default value
13.1 EOL mode
Normal/Dual
Normal
13.2 EOL class
10 A, 10, 20, 30
10
13.3 EOL dual class
10 A, 10, 20, 30
20
13.5 EOL operation
Off, Stop-Manual,
Stop-Automatic, Indication
Stop-Manual
13.10 Locked rotor operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
14.5 Current underload operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
15.4 Over voltage operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
15.7 Under voltage operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
16.2 Phase reversal operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
16.9 By-pass open operation
Off, Stop-Manual,
Stop-Automatic, Indication
Indication
18.5 Earth fault trip time
0,1s ... 10,0s
0,5s
18.7 Earth fault operation
Off, Stop-Manual,
Stop-Automatic, Indication
Off
Warnings
Parameter name
Setting range
Default value
20.1EOL level
40 ... 99%
90%
20.3 EOL warning
On/Off
Off
20.7 Locked rotor
On/Off
Off
20.9 Thyristor overload
On/Off
Off
21.5 Current underload
On/Off
Off
22.4 Over voltage
On/Off
Off
22.8 Under voltage
On/Off
Off
23.1 EOL time-to-trip
On/Off
Off
23.4 THD(U) level
1...10%
10%
23.6 THD(U)
On/Off
Off
24.1 Number of starts limit
1 ... 65535
65535
24.3 Number of starts
On/Off
Off
23.8 Short circuit
On/Off
Off