Commissioning
CI/FEX300/FEX500-EN
FEX300, FEX500
EN - 57
Easy Setup
Pulses per Unit
10.000 / m
³
Next
Edit
25.
Use
to call up the edit mode.
26.
Use
or
to set the required value.
27.
Use
to confirm your setting.
Easy Setup
Pulse Width
30.00 ms
Next
Edit
28.
Use
to call up the edit mode.
29.
Use
or
to set the required pulse width.
30.
Use
to confirm your setting.
Easy Setup
Damping
30.00 ms
Next
Edit
31.
Use
to call up the edit mode.
32.
Use
or
to set the required damping.
33.
Use
to confirm your setting.
Easy Setup
Iout at Alarm
High Alarm
Next
Edit
34.
Use
to call up the edit mode.
35.
Use
or
to select the alarm mode.
36.
Use
to confirm your selection.
Easy Setup
Low Alarm Value
3.5000 mA
Next
Edit
37.
Use
to call up the edit mode.
38.
Use
or
to set the required current value for
low alarm.
39.
Use
to confirm your selection.
Easy Setup
High Alarm Value
21.800 mA
Next
Edit
40.
Use
to call up the edit mode.
41.
Use
or
to set the required current value for
high alarm.
42.
Use
to confirm your selection.