Manual Power Quality Filter PQFS
Electrical design and installation 51
•
The l (S2) terminal of the line 1 CT (L1, Red, U) must be connected to
terminal X21-2 of the filter.
•
The k (S1) terminal of the line 2 CT (L2, Yellow, V) must be connected to
terminal X214 of the filter.
•
The l (S2) terminal of the line 2 CT (L2, Yellow, V) must be connected to
terminal X21-5 of the filter.
•
The k (S1) terminal of the line 3 CT (L3, Blue, W) must be connected to
terminal X21-7 of the filter.
•
The l (S2) terminal of the line 3 CT (L3, Blue, W) must be connected to
terminal X21-8 of the filter.
−
The CT connection terminal X21 is located at the middle of the top plate of the
filter (Cf.
L1
L2
L3
Load side
Supply side
K
L
k
l
K
L
k
l
K
L
k
l
PQF
X21.1
X21.2
X21.3
X21.4
X21.5
X21.6
X21.7
X21.8
X21.9
L1
L2
L3
To X21.1/X21.2
To X21.4/X21.5
To X21.7/X21.8
K = P1, L = P2, k = S1, l = S2
N
N
Figure 33: Basic CT connection example for a single unit active filter
CT connection terminal X21
Figure 34: Location of the CT connection terminal X21 in the PQFS
The terminal block X21 can handle control cable wiring with sections from 2.5 mm² to
10 mm².
In addition to the 6-wire CT cabling approach shown in
approach may also be used. This approach is illustrated in
. In this case the CT
secondary terminal to which the guard circuit is connected is interconnected between
the CTs and also on the filter terminal X21. One common cable is used for this terminal.