Manual Power Quality Filter PQFS
Technical specifications 213
Can be used to monitor the filter state (e.g. filter on/off or
specific filter warnings/alarms) and the network state.
Alarm contact
1 universal alarm contact with two complimentary outputs
(NO/NC) on PQF-Manager. Triggered by any fault.
Maximum continuous rating: 250 Vac/1.5 A
Filter losses
Typical values
Maximum values
Unit rating: 30 A
0.7 kW
≤
1.5 kW
Unit rating: 45 A
1 kW
≤
1.8 kW
Unit rating: 60 A
1.3 kW
≤
2.1 kW
Unit rating: 70 A
1.8 kW
≤
2.6 kW
Unit rating: 80 A
2.1 kW
≤
2.9 kW
Unit rating: 90 A
2.4 kW
≤
3.2 kW
Unit rating: 100 A
2.7 kW
≤
3.5 kW
Unit rating: 120 A
3.5 kW
≤
4.3 kW
Phase to earth resistance
1.67 M
Ω
/filter unit
Noise intensity
30A - 60A: 65.3 dBA typically
70A - 100A: 68.4 dBA typically
120A : 70.9 dBA typically
Communication
Through PQF-Manager display.
Through Modbus RTU (with optional RS485 Modbus
Adapter).
Through Modbus TCP (with Ethernet).
Through dedicated optional software PQ-link (with USB-
Ethernet).
Programming
Through PQF-Manager display.
Through USB-Ethernet with dedicated optional software
(PQ-Link).
Fuse information
Main circuit fuses
Not included
Auxiliary circuit fuses
French Ferrule 10 x 38 gG/gl, 6A, 500V, Isc ~120kA
Main options
PQ-Link software
RS-485 Modbus adapter
Easy connection box for power cables
Cable extension kit for PQF-Manager
Remark:
(a)
Under exceptional circumstances other limits may be reached before the RMS current limit (e.g.
temperature limit, peak current limit, peak voltage limit).