Environmental Considerations
To operate the UPS at the best efficiency point, your installation site should meet the environmental
parameters outlined in this manual. Excessive amount of dust or moisture in the operating environment
may cause damage or lead to malfunction. The UPS should be always protected from the outside
weather and sunshine. The operating environment must meet the weight, airflow, size and clearance
requirements specified in the technical datasheet.
Under no circumstances, the UPS should be installed in an airtight room, in the presence of flammable
gases, or in an environment exceeding environmental requirements here below.
An ambient temperature of +20°C to +25°C is recommended to achieve a long life of the UPS and
batteries. The cooling air entering the UPS must not 40 °C and the humidity should be below
95% (non-condensing)
.
1.3
Declaration of Safety conformity and CE marking
PowerValue 11 RT is designed, manufactured and commercialized in accordance with the standard
EN ISO 9001 of Quality Management Systems.
These products are in conformity with the directives:
•
2014/35/EU Low voltage directive
•
2014/30/EU Electromagnetic Compatibility directive (EMC)
•
2011/65/EU Restriction of the use of certain hazardous substances (RoHS) directive
and with the following product standards:
Product Standards
Safety
IEC/EN 62040-1:2008+A1:2013
EMC
IEC/EN 62040-2:2006
RoHS
IEC/EN50581:2012
Figure 1: Standards
1.4
Inquiries
Address inquiries about the UPS to the local office or agent authorized by the supplier. Please note the
type code and the serial number of the equipment and contact your nearest agent authorized by the
supplier. The serial number is shown in the nameplate of the product. For further information on
troubleshooting, go to Section 7.