Modifications reserved
Page 38/49
Auto bypass
The automatic bypass can be disabled
for countries where the power supply is
very unstable. UPS runs only online or
on battery.
enabled/disabled
disabled
Short circuit
clearance
- When enabled, short circuit will last for
4s before cutting off the output. If short
circuit is removed during this time, the
UPS will continue to run normally.
- When disabled, short circuit will only
last for 100ms before UPS output is cut
off.
enabled/disabled
disabled
Bypass voltage low
limit
When the voltage in the bypass is below
this limit, the UPS changes running
mode.
176~215V
184V
Bypass voltage
high limit
When the voltage in the bypass is above
this limit, the UPS changes running
mode.
245~276V
264V
Bypass frequency
low limit
When the frequency in the bypass is
below this limit, the UPS changes
running mode.
40~49.5 Hz
45 Hz
Bypass frequency
high limit
When the frequency in the bypass is
above this limit, the UPS changes
running mode.
50.5~70 Hz
55 Hz
Eco-mode voltage
low limit
When the voltage in the bypass is below
this limit, the UPS changes running
mode.
1%~10%
5%
Eco-mode voltage
high limit
When the voltage in the bypass is above
this limit, the UPS changes running
mode.
1%~10%
5%
Eco-mode
frequency low limit
When the frequency in the bypass is
below this limit, the UPS changes
running mode.
1%~10%
5%
Eco-mode
frequency high limit
When the frequency in the bypass is
above this limit, the UPS changes
running mode.
1%~10%
5%
External Battery
modules***
Define the number of external battery
modules.
0 - 97
0
Set running time
Used to reset the UPS running time for
tests purposes.
Day:hour:minute:second
0000:0000:00~9999:23:59:5
9
Running
time
LCD contrast
Change the contrast in the LCD display
-5~+5
0
Battery remaining
time
When enabled, the battery remaining
time is displayed in the menu
measurements
enabled/disabled
enabled
Table 5: Settings menu information
**Read Section 5.2, before using ECO-mode or converter function.
***Ensure the real battery quantity is same as indicated in the settings not to damage the batteries.
Example: Setting the rated output voltage value (figure 25).