CLEARANCES
10 kVA
20 kVA
MINIMUM CLEARANCES FOR SINGLE UPS
A
50 cm
50 cm
B
50 cm
50 cm
C
0 cm
0 cm
D
5 cm
5 cm
MINIMUM CLEARANCES FOR UPS PLUS OTHER CABINETS IN ROW
A
50 cm
B
50 cm
50 cm
C
0 cm
0 cm
D
5 cm
5 cm
50 cm
PowerValue 11/31 T Technical Specifications
Page 11
HEAT DISSIPATION
10 kVA
20 kVA
Air-flow
From front to back
Heat dissipation with 100%
linear load
669 W / 2282.7 BTU
1207 W / 4118.5 BTU
Heat dissipation with 100%
non-lin. load (acc. to 62040-3)
669 W / 2282.7 BTU
1207 W / 4118.5 BTU
Air-flow (25° - 30°) with 100%
non-linear load
133 m
3
/h
240 m
3
/h
Heat Dissipation without load
160 W
170 W