Cable sections and fuse ratings recommended according to (IEC 60950-1)
Alternatively, local standards to be respected!
CABLES & FUSES
RATINGS
10 kVA (1-1)
10 kVA (3-1)
20 kVA (1-1)
SINGLE INPUT FEED
Input fuse A-Type: gL or CB
1 x 63A
3 x 63A
1 x 100A
3 x 100A
Input cable A
3 x 16mm
2
5 x 16mm
2
3 x 25mm
2
5 x 25mm
2
Output cable D
3 x 16mm
2
3 x 16mm
2
3 x 25mm
2
3 x 25mm
2
Battery fuse E-Type: gR or CB
2 x 40A
2 x 40A
2 x 80A
2 x 80A
Battery cable E
3 x 6mm
2
3 x 6mm
2
3 x 16mm
2
3 x 16mm
2
DUAL INPUT FEED
Input fuse B-Type: gL or CB
1 x 63A
3 x 25A
1 x 100A
3 x 50A
Input Cable B
3 x 16mm
2
5 x 4mm
2
3 x 25mm
2
5 x 10mm
2
Input fuse C-Type: gR or CB
1 x 63A
1 x 63A
1 x 100A
1 x 100A
Input cable C
3 x 16mm
2
3 x 16mm
2
3 x 25mm
2
3 x 25mm
2
Output cable D
3 x 16mm
2
3 x 16mm
2
3 x 25mm
2
3 x 25mm
2
Battery fuse E-Type: gR or CB
2 x 40A
2 x 40A
2 x 80A
2 x 80A
Battery cable E
3 x 6mm
2
3 x 6mm
2
3 x 16mm
2
3 x 16mm
2
20 kVA (3-1)
PowerValue 11/31 T Technical Specifications