Appendix B – Parameter Scaling
Installation and Start-up Guide for NMBP-01
B-3
ACTUAL SIGNALS
Parameter
Short Name
4xxxx
Register
Description
Scaling
PROCESS SPEED
P SPEED
40101
Process speed
-100 -100 %
of the value defined with
Parameter 20.2 (DTC Control Mode) or
Parameter 20.8 (SCALAR Control Mode)
SPEED
SPEED
40102
Motor speed
-20000 -100 %
FREQUENCY
FREQ
40103
Inverter output frequency
-100
-1 Hz
CURRENT
CURRENT
40104
Motor current
10 1 A
TORQUE
TORQUE
40105
Motor torque
-10000
-100 %
of motor nominal torque
POWER
POWER
40106
Motor power
10000
100 %
of motor nominal power
DC BUS VOLTAGE V
DC BUS V
40107
DC bus voltage of ACS 600
1 1 V
MAINS VOLTAGE
MAINS V
40108
Calculated supply voltage
1 1 V
OUTPUT VOLTAGE
OUT VOLT
40109
Calculated motor voltage
1
1 V
ACS 600 TEMP
ACS TEMP
40110
Temperature of the heatsink
1
1 °C
EXTERNAL REF 1
EXT REF1
40111
External reference 1
1 1 rpm
EXTERNAL REF 2
EXT REF2
40112
External reference 2
10000
100 %
of motor max. speed / nominal torque /
max. process reference (depending on
the ACS 600 macro selected)
CTRL LOCATION
CTRL LOC
40113
Active control location
1 = EXT2; 2 = LOCAL; 3 = EXT1
OP HOUR COUNTER
OP HOURS
40114
Elapsed time counter
1 1 h
KILOWATT HOURS
KW HOURS
40115
kWh meter
1 1 kWh
APPL BLOCK OUTPUT
APPL OUT
40116
The reference given as an
output from the application
(PID controller output, etc.)
10000
100 %
DI6-1 STATUS
DI6-1
40117
Status of digital inputs
000000 – 111111
AI1 (V)
AI1 (V)
40118
Value of Analogue input 1
1
0.01 V
AI2 (mA)
AI2 (mA)
40119
Value of Analogue input 2
1
1 mA
AI3 (mA)
AI3 (mA)
40120
Value of Analogue input 3
1
1 mA
RO3-1 STATUS
RO3-1
40121
Status of relay outputs
AO1 (mA)
AO1 (mA)
40122
Value of Analogue output 1
1
1 mA
AO2 (mA)
AO2 (mA)
40123
Value of Analogue output 2
1
1 mA
ACTUAL VALUE 1
ACT VAL1
40124
PID controller Actual value 1
Available only if the PID
Macro is selected
10000
100 %
ACTUAL VALUE 2
ACT VAL2
40125
PID controller Actual value 2
Available only if the PID
Macro is selected
10000
100 %
CONTROL
DEVIATION
CONT DEV
40126
The difference between the
reference given by the user
and the actual reference the
ACS 600 is following
-10000
-100 %
100 %
100
100 %
20000
1 Hz
100
10000
100 %
0
0 %
0
0 %
0
0 %
0 %
0
0 %
0
10000
100 %