![ABB NMBP-01 Installation And Startup Manual Download Page 33](http://html.mh-extra.com/html/abb/nmbp-01/nmbp-01_installation-and-startup-manual_2754033.webp)
Installation and Start-up Guide for NMBP-01
5-11
Data set 4 - STATUS
This data set is used to read back the drive status using the communication
network. This is a 16-bit word, where each of the bits have its own, defined
meaning. The bits are listed in Table 5-3 below.
Table 5-3 The Status Word.
Bit
Name
Description
0
READY
1 = Drive Ready to Start
0 = Initialising, or Initialisation Error
1
RUN ENABLE
1 = Enabled
0 = Not Enabled
2
reserved
3
RUNNING
1 = Drive Running w. Selected Reference
0 = Drive Stopped
4
QUICK_STOP
1 = Quick Stop Active
0 = No Quick Stop
5
REMOTE
1 = Drive in Remote Mode
0 = Drive in Local Mode
6
reserved
7
AT_SETPOINT
1 = Drive at Reference
0 = Drive not at Reference
8
FAULTED
1 = Active Fault
0 = No Active Faults
9
WARNING
1 = Active Warning
0 = No Active Warnings
10
LIMIT
1 = Drive at Limit
0 = No Active Limits
11 – 15
reserved