Chapter 6 – Communication
6-2
NMBA-01 Installation and Start-up Guide
Table 6-1 Parameter Mapping
The register addresses which are not allocated to any drive parameter
or data set are invalid. No reads or writes are allowed for these
addresses. If there is an attempt to read or write outside the parameter
addresses, the Modbus interface will return an exception code to the
controller.
Refer to the drive manuals for its data sets, group and parameter
numbers supported.
4GGPP
GG
PP
Data sets
40001 – 40096
00 Data sets
01 Data word 1.1
02 Data word 1.2
03 Data word 1.3
04 Data word 2.1
05 Data word 2.2
06 Data word 2.3
07 Data word 3.1
...
94 Data word 32.1
95 Data word 32.2
96 Data word 32.3
Parameters
40101 – 40199
01 Group 01
01 Parameter 01
02 Parameter 02
...
99 Parameter 99
40201 – 40299
02 Group 02
01 Parameter 01
02 Parameter 02
...
99 Parameter 99
…
...
...
49901 – 49999
99 Group 99
01 Parameter 01
…
99 Parameter 99