![ABB NMBA-01 Installation And Startup Manual Download Page 18](http://html.mh-extra.com/html/abb/nmba-01/nmba-01_installation-and-startup-manual_2753018.webp)
Chapter 4 – Electrical Installation
4-2
NMBA-01 Installation and Start-up Guide
NMBA-01 Connections
Figure 4-2 Fibre optic link connecting the NMBA-01 adapter
to the drive.
The NMBA-01 module is connected to the drive using a fibre optic
cable link. Consult the drive documentation as to the corresponding
terminals inside the drive.
The bus cable and the external power supply are connected to terminal
block X2 on the NMBA-01.
Table 4-1 Description of terminal block X2.
X2
Description
1
D(P)
D(P) = B = Data Positive (Conductor 1 in twisted pair)
D(N) = A = Data Negative (Conductor 2 in twisted pair)
DG = Data Ground
2
D(N)
3
DG
4
SHF
Cable screen AC earthing (via an RC filter)
5
SH
Cable screen earthing (directly earthed)
6 0V
Power supply for the module (24 V d.c. ± 10 %); screened cable.
7
+24 V
8
PE
Earth
NMBA-01
MODBUS
ADAPTER
BU S
TER MIN ATION
O N
O FF
X2
PE
SH
SHF
D G
D(N)
D(P)
TXD
RXD
XM IT
REC
ER ROR
+24V
0V
ABB Drive
R
T
1
2
3
4
5
6
7
8
X2:
T
DDCS
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor