Chapter 7 – Fault Tracing
7-2
NMBA-01 Installation and Start-up Guide
Status LEDs
The NMBA-01 has three status LEDs. These are from top to bottom:
•
XMIT LED. This LED will flash each time the NMBA-01 transmits a
response or an exception on the Modbus network.
•
REC LED. This LED will flash each time the NMBA-01 receives a
command from the Modbus network.
•
ERROR LED for combined error and module status indication. This
LED will flash for the following reasons:
-
If the received command had a parity error.
-
If the received command had a CRC error.
-
If the received command was not supported by the NMBA-01
module. In this case the
XMIT LED will also flash.
-
If the NMBA-01 module has found an error. The error codes are
described in Table 7-2 below.
Module Diagnostics
On module power-up, the NMBA-01 goes through a power-up self-test
sequence. During this, the test state is indicated by the front three
LEDs. The normal power-up procedure is as follows:
•
All LEDs are turned on for the duration of the RAM/ROM test. If the
test is passed, all LEDs will be turned off.
•
The
ERROR LED will flash rapidly for few seconds as the DDCS link
between the NMBA-01 and the drive is initialised.
•
REC and XMIT LEDs will flash according to the data transferred
between the NMBA-01 and the drive.
Table 7-1 Modbus Error Codes during Initialization.
Flash Code
Status
Correction
XMIT, REC, and
ERROR LEDs on
ROM checksum test failed
Hardware failure. Replace NMBA.
REC and ERROR
LEDs on
RAM test failed
Hardware failure. Replace NMBA.
ERROR LED on
DDCS ASIC register
access test failed
Hardware failure. Replace NMBA.