
Navigator 500
Sodium analyzer
Appendix C – Multiple wet-section setup
78
OI/ASO550–EN Rev. G
Appendix C – Multiple wet-section setup
A single Navigator 540 transmitter can monitor up to 4 wet-sections. The wet-sections can be any combination of the three Navigator
500 parameters – sodium, low level dissolved oxygen and hydrazine. Note that the transmitter cannot monitor more than 1 wet-
section if the wet-section is a multi-stream sodium.
If an additional wet-section is added to a transmitter, the procedures in Sections C.1 and C.2 must be performed.
C.1 Configuring the device address
The unique device address assigned to the wet-section (1 to 4), enables the transmitter to identify the wet-section on the data
transmission link. Each wet-section must have its own unique address. The address can be set by SW1 as shown in Table C.1 and
Fig. C.1. LEDs D4 and D5 indicate the slave address of the PCB.
C.2 Serial connections
Each wet-section must be connected in a 'daisy chain' format as shown in Fig. C.2.
Slave address
SW1.1
SW1.2
LED D4
LED D5
1
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
ON
3
ON
OFF
ON
OFF
4
ON
ON
ON
ON
Table C.1 Configuring the device address
Fig. C.1 Configuration DIP switch SW1 and LED D4 / D5 location
Fig. C.2 Serial connections
Note.
The total cable length between the transmitter and the last wet-section must not exceed 30 m (98 ft.).
B R
Scr
G W
1 3 5 7 9 1 1 13 15 17 19 21 23 25 27 29 31 33 3
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
D5
D4
ON
1 2
SW1
ON
1 2
SW1
SW1.1
OFF position
SW1.2
ON position
Configuration DIP switch SW1
LED D4 and LED D5
Terminals G and W
Navigator 500
Wet-section 1
Wet-section 2
Wet-section 3
Wet-section 4
Red
Black
Green
White
Screen
R
B
G
W
SCR
R
B
G
W
SCR
R
B
G
W
SCR
R
B
G
W
SCR