34
LMT10 0 A N D LMT 20 0 |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER S | FF O I/L M T 10 0/ 2 0 0/FF - EN R E V. A
Menu: Easy Setup (continued)
Menu/Parameter
Value Range
Description
Easy Setup
Language
English, Chinese, Portuguese, German, Spanish, French,
Italian, Russian
Menu language options
Level Unit (also Volume Unit or
Flow Unit depending on
configurations)
• Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, cubic meters, cubic inches, cubic feet, cubic
yards, gallons, imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/hour, imperial gallons/day,
barrels/second, barrels/minutes, barrels/hour,
barrels/day, cubic meters/second, cubic meters/
minute, cubic meters/hour, cubic meters/day, cubic
feet/second, cubic feet/ minute, cubic feet/hour,
cubic feet/day
Defines unit of measure for primary variable
Level LRV (also Volume Level LRV or
Flow LRV depending on
configurations)
Non-linearized
Minus 10% to half of probe length
Linearized
-999999999 to 999999999
Sets lower point which is also the lower range value of the
measuring span
Level URV (also Volume Level URV
or Flow URV depending on
configurations)
Non-linearized
Half to 20% beyond probe length
Linearized
-999999999 to 999999999
Sets upper point output point which is also the upper
range value for the measuring span
Interface Level LRV (Only displays
when two floats are attached May
also display as Volume Interface
LRV, depending on configuration )
Sets lower range value for liquid interface measuring
span
Interface Level URV (Only displays
when two floats are attached May
also display as Volume Interface
URV, depending on configuration )
Sets upper range value for liquid interface measuring
span
Level Damping Time
0.1 - 60 seconds
Allows signal smoothing of the signal
Display 1 Line 1 View
Raw Level, Distance/Ullage, Level, Interface
Select variable to be viewed on display
Tag
alphanumeric
User defined. 32 characters available.