Page 7
© 2021 ABB. All rights reserved.
QUICK START GUIDE
Default Voltage Settings and Ranges
Range
Valve
-
Reg
Flooded
NiCd
Rectifier Float Selective High Voltage Shutdown
-
50 to
-
60V
58.50
58.50
58.50
High Float Voltage Major Alarm
-
50 to
-
60V
57.00
57.00
57.00
High Float Voltage Minor Alarm
-
50 to
-
60V
56.00
56.00
56.00
Rectifier/System Float Voltage
-
42 to
-
56.5V
54.48
52.08
54.40
Battery on Discharge Float Alarm
-
46 to
-
55V
51.00
50.00
51.00
Very Low Float Voltage Alarm
-
40 to
-
51V
46.00
46.00
46.00
Rectifier On Threshold
-
40 to
-
51V
44.00
44.00
44.00
Front
Display
Menu
Map