QUICK START GUIDE

 

Two controller options are available; CC109128402 NE843A Pulsar slot controller or CC109132024 Millennium II Rack 
mounted controller. Controller product manuals are available at 

abbpowerconversion.com

 

The Pulsar slot controller mounts in the left most position of the top shelf (as shown in the diagram on page 1). All 
controller  connections  are  accessible  with  the  controller  installed.  Refer  to  the  table  below  for  detailed  alarm 
connection  information.  Before  in

-

  stalling  the  controller  configure  the  bus  reference  voltage  and  alarm  output 

jumpers;

 

1.

 

Set Jumper 11 to (+) for +24Vdc systems or (

-

) for 

-

48V/

-

24V (Factory Default) systems.

 

2.

 

Set jumpers 1 thru 10 for the ten alarm relays as 

Close

” 

or 

Open

” 

on alarm; Factory default setting is 

Close

” 

on alarm. The 

Alarm relay jumpers are located under the sliding cover on top of the controller, see figure below.

 

Note: The optional Millennium II rack mount controller can be used instead of the Pulsar when additional controller 
features are required. See the Millennium II Product Manual at  

abbpowerconversion.com

 for more information.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                               System reference voltage and alarm output jumpers.

 

J1 Optional system 
Interface. See table 
below.

 

J2 Thermal probes. See 
back page.

 

J3 Auxiliary Inputs

 

J5 LAN

 

Bus reference V and 
Alarm Relay Jumpers 

under cover

 

J4 Alarm Outputs

 

Close on Alarm

 

 

Open on Alarm

 

10

 

9

 

8

 

7

 

6

 

5

 

4

 

3

 

2

 

1

 

11

 

+24

 

-

48V /+24 V

 

Summary of Contents for Infinity B G240 System +24V/-48V

Page 1: ...ectifiers 41 42 31 32 21 22 11 12 13 14 23 24 33 34 43 44 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 L2 0 JJll111111111111111 aii11111m1111i1i tllllllllllllllllll n1111m1111if11 lllllllllllllllllb of 11 1IIIIIIIIIIIIIIUU J IIIIIIIIIIIIIIIUlb u11111m111iiiw 11111111111111111111 nfif11 um11111111 1ll111111lllllllllb m11111m111mr i iHHlllllllllllllb i...

Page 2: ...tach the individual 10 AWG AC input wires for each position and torque the wire clamps to 10 inch lbs 2 For applications using one ac feed for every two rectifiers Use a pair of needle nose pliers to remove the divider between the individual rectifier wire clamps that will share the ac input 3 Install a strap between the two terminal blocks Secure the strap in posi tion with two screws and torque ...

Page 3: ...Set Jumper 11 to for 24Vdc systems or for 48V 24V Factory Default systems 2 Set jumpers 1 thru 10 for the ten alarm relays as Close or Open on alarm Factory default setting is Close on alarm The Alarm relay jumpers are located under the sliding cover on top of the controller see figure below Note The optional Millennium II rack mount controller can be used instead of the Pulsar when additional con...

Page 4: ...nt O BK Fuse Alarm Major 24V Open Battery String Fuse Alarm Major 48V Standard Controller Alarm Output Defaults Pin Color Option 1 Color Option 2 PCR Power Critical BL BL PCR_C Power Critical_C 11 BL BK PMJ Power Major PMJ_C Power Major_C 12 O BK PMN Power Minor PMN_C Power Minor_C 13 G BK R1 Battery On Discharge BR R1_C Battery On Discharge_C BD_C 14 W BK R2 Very Low Voltage VLV BK R2_C Very Low ...

Page 5: ... rectifiers and converters The outputs are located on the rear of the shelf The shelf is designed to distribute bulk power only there are no DC output protectors in the shelf Lug landings accommodate 3 8 di ameter lugs on 1 centers spaced 1 75 apart Three 750 MCM Flex lugs can be connected per bus Bus extensions are provided to land four additional cables back to back Standard Controller Alarm Pin...

Page 6: ...ype the default IP address in the web browser address field Server mode is a temporary setting once configuration is complete reset the controller to Client or Static before connecting to the network Static is the factory default setting and the typical setting for most networks Warning Do not connect J5 LAN port to a network when set to Server Controller Alarm Status The display changes colors Gr...

Page 7: ... 58 50 58 50 High Float Voltage Major Alarm 50 to 60V 57 00 57 00 57 00 High Float Voltage Minor Alarm 50 to 60V 56 00 56 00 56 00 Rectifier System Float Voltage 42 to 56 5V 54 48 52 08 54 40 Battery on Discharge Float Alarm 46 to 55V 51 00 50 00 51 00 Very Low Float Voltage Alarm 40 to 51V 46 00 46 00 46 00 Rectifier On Threshold 40 to 51V 44 00 44 00 44 00 Front Display Menu Map ...

Page 8: ...ccomplished with a Daisy Chained series of QS873 probes connected to J2 The Probes are used to monitor battery temperature and mid string voltage ES771 required to monitor voltage Bolt the Probe under the terminal connector hardware NOT under the connecting lug Temperature monitoring Temperature and voltage monitoring ...

Page 9: ...eed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB...

Reviews: