30 2CDC502099D0211 Rev. A | IPR/S 3.5.1
Multicast Address
(default = 224.0.23.12)
Options:
224.0.23.12
The routing multicast address defines the target address of the IP telegrams of the IPR/S. The preset
address 224.0.23.12 is the defined address for the KNXnet/IP from the KNX Association in conjunction
with IANA for KNX IP devices. This address should be retained and changed only if the existing network
demands that another address from the range 224.0.0.0 to 239.255.255.255 (reserved range for multicast
addresses) be used.
The routing multicast address is set in the ETS in the view
Topology
(topology selection; the routing
multicast address can then be set on the
Settings
tab in the Properties window):
Important
All IP Router Secure devices or other KNXnet/IP devices that are required to exchange telegrams on
the IP-network must use the same routing multicast address.
3.3
Group objects
The IP Router Secure IPR/S has no KNX group objects.