Commissioning
42 2CDC505163D0201 | AA/S 4.1.2, AA/A 2.1.2
Switch on at
Options:
User-defined value
Last output value
This parameter allows you to choose a switch-on value of between 0...100 % or to switch back on at the
last output value before switching off.
In order to switch on, the group object that switches the load (e.g. via Switch Actuator SA/S) is also linked
to the group object
Switch
for the associated Analogue Actuator channel. Alternatively, the switch actuator
status response (
Status Switch
) can be linked with the input object
Switch
of the Analogue Actuator. Or in
reverse order, the group object
Status Switch
of the Analogue Actuator can be linked with the group object
Switch
of the Switch Actuator.
Selection of the option
User-defined value
:
Dependent parameters:
User-defined value in
defined input range in % [0...100]
Options:
0…80…100
This can be entered in 1 % increments.
Note
After a device download, the upper dimming limit is used as the last brightness value.
Dimming speed for [0...100%] while
switching in s [0...255]
Options:
0
…100
The value selected indicates the speed required to switch the lamp from 0 to 100 %. If switching between
other values, the duration is calculated based on this value.
Note
The group object
Status Switch
will change the status from "Off" to "On" if the input value is higher than
the smallest defined input value.
This will also apply with the
Characteristic
function if an output value higher than the smallest physical
value has been assigned to the smallest input value.
Summary of Contents for i-bus KNX AA/A 2.1.2
Page 1: ...ABB i bus KNX Analogue Actuator AA S 4 1 2 AA A 2 1 2 Product Manual ...
Page 2: ......
Page 4: ......
Page 20: ......
Page 51: ...ABB i bus KNX Commissioning AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 49 Priorities ...
Page 65: ...ABB i bus KNX Appendix AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 63 Notes ...
Page 66: ...ABB i bus KNX Appendix 64 2CDC505163D0201 AA S 4 1 2 AA A 2 1 2 Notes ...
Page 67: ......