ABB i-bus
®
KNX
Commissioning
AA/S 4.1.2, AA/A 2.1.2 | 2CDC505163D0201 57
3.3.3.2
Group objects Channel A
No.
Function
Object name
Data type
Flags
10
Status Actual value
Channel A
Variable
DPT variable
C, R, T
This group object is always enabled if the parameter
Type of output
deactivated.
It reflects the status of the output (output value) in the form of the user-selected input value format.
The following values can be sent:
1-
byte value [0…100] %
DPT
5.001
1-byte value [0...+255]
DPT
5,005
1-byte value [-128...+127]
DPT
6.010
2-byte value [0...+65,535]
DPT
7.001
2-byte value [-32,768...+32,767]
DPT
8.001
2-byte value (floating point)
DPT
9.0xx
4-byte value (IEEE float. point)
DPT
14.0xx
11
Status Switch
Channel A
1 bit
DPT 1.001
C, R, T
This group object is enabled if the parameter
Enable function Dimming
Yes
.
For the group object to be sent, the parameter
Send status values
in
On change
.
It shows whether the input value has a higher value than the lowest threshold in the defined input range. The value is set to
"On" (1) if a new value is written via the group object
Input value,
or if the output is switched on using the object
Dimming
,
or if the output is switched on using the object
Switch
.
20
Alarm
Channel A
1 bit
DPT 1.005
C, R, T
This group object is enabled unless the parameter
Activate cyclical
parameter in
set to
No
.
It shows whether the monitoring time for cyclical monitoring has expired and if the output has therefore been switched to
the value set for this eventuality.
Telegram value:
0 = Cyclical monitoring time has not been exceeded
1 = Cyclical monitoring time has been exceeded
21
Fault at output
Channel A
1 bit
DPT 1.005
C, R, T
This group object is enabled unless the parameter
Type of output
It shows whether there is a fault at the output.
Telegram value:
0 = No fault at output
1 = Fault at output
22
Voltage output value
Channel A
2 bytes
DPT 9.02x
C, R, T
Current output value
This group object is enabled unless the parameter
Type of output
Depending on the output type (voltage or current) the DPT is set accordingly:
voltage, DPT 9.020/current, DPT 9.021.
The group object contains the physical output value for the channel present at the output.
Summary of Contents for i-bus KNX AA/A 2.1.2
Page 1: ...ABB i bus KNX Analogue Actuator AA S 4 1 2 AA A 2 1 2 Product Manual ...
Page 2: ......
Page 4: ......
Page 20: ......
Page 51: ...ABB i bus KNX Commissioning AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 49 Priorities ...
Page 65: ...ABB i bus KNX Appendix AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 63 Notes ...
Page 66: ...ABB i bus KNX Appendix 64 2CDC505163D0201 AA S 4 1 2 AA A 2 1 2 Notes ...
Page 67: ......