1.2.2 Operating mechanism
The operating mechanism has a spring charging device which can be
operated by motor or by hand. Once a closing command has been given it is always
completed by the breaker; this is important in the event of short circuit. Since, the
circuit breaker closes completely before it opens, the correct contact speed and full
breaking capacity are obtained. The operating device has compression springs for
closing and opening. The opening spring is charged automatically when the breaker
is closed. A closed breaker with charged closing springs can be operated open - close
- open without intermediate motor or manual charging and the breaker can therefore
be used for auto re-closing. Charging of the closing spring can be discharged by
disconnecting the voltage to the motor and manually operate the breaker close -
open.
An indication shows whether the closing spring are charged or not and the number of
opening operations are recorded on a counter.
The motor can be supplied via a station battery, a network or via a voltage transformer
with a limit load of at least 300 VA. The motor starts after each closing operation and
charges the closing springs within 9 seconds. The breaker is fitted with a knob for
mechanical openings and with magnetic coils for closing and openings. The same
operating mechanism is used for all types of HPA breaker.
The construction of the operating mechanism is shown in fig. 4. The device has two
shafts. The lower shaft (6) is connected to the breaker poles via links and is directly
actuated by the openings springs (5). The upper shaft (3) is connected directly to the
closing spring (11). These two shafts are linked via the driving disc (9) and the link
(12), and by the trip free device (14). The upper shaft is also connected to the charging
device via the trip-free device (1) and the link (4).
The latching and trip-free devices (1) and (14) are of the same type that have been
used in ABB equipment since 1950 and have proven extremely reliable.
The motor operated unit consists of a toothed transmission gear with an eccentrically
driven tooth wheel as a last step. The operating device also contains auxiliary
contacts and trip coils.
(6)
Fig - 4
(Principle diagram of Circuit Breaker)
Summary of Contents for HPA 12kV
Page 7: ...Fig 3b HPA breaker pole for 36 kV ...
Page 9: ... 7 Fig 5 Circuit Breaker ...
Page 13: ...Fig 7A Maintenance schedule for frequently operated breaker type HPA 1VYN400290 005 11 ...
Page 14: ...Fig 7B Maintenance schedule for frequently operated breaker type HPA 1VYN400290 005 12 ...
Page 15: ...Electrical endurance HPA 13 ...
Page 29: ......