64
H I PE RG UA R D M V U PS
US ER M A N UA L
W5.146
Sout racked out
Output Switch circuit breaker is detected as being racked out
from its cubicle.
W5.149
Sout relay warning
Output switch circuit breaker relay warning.
W5.150
Sout relay fault
Output switch circuit breaker relay fault is detected.
W5.155
Sabp unexpectedly ready to transi-
tion
Automatic Bypass switch circuit breaker reports as ready to
transition before software thinks it should.
W5.156
Sapb racked out
Automatic Bypass switch circuit breaker is detected as being
racked out from its cubicle.
W5.158
Sabp relay warning
Automatic Bypass switch circuit breaker relay warning.
W5.159
Sabp relay fault
Automatic Bypass switch circuit breaker relay fault is de-
tected.
W5.162
Sabp open request & FB mismatch
In the Automatic Bypass switch, there has been a mismatch
detected between "open" request and "open" Feedback.
W5.164
Output current high
The output current loading on the system exceeds system
nominal rated current by more than a certain percentage.
W5.165
Output current too high
The system output current has been detected as exceeding
the maximum allowable.
W5.170
Output voltage low
The RMS value of output line voltage has fallen below the low
voltage threshold value.
W5.177
DRP Ctrl comms link invalid
Demand Response Power Controller communications link not
valid.
W5.179
DRP Ctrl SOC at min or max limit
Demand Response Power Controller has determined state of
charge of energy storage is at minimum or maximum limit.
W5.180
Energy Storage enclosure external IO
inputs invalid
Energy Storage enclosure MODBUS INPUTS & OUTPUTS NOT
VALID.
W5.182
MVM enclosure external IO inputs in-
valid
MVM enclosure MODBUS INPUTS & OUTPUTS NOT VALID.
W5.184
Internally fed 24V PSU failed
Possible power supply issue or malfunction in APS enclosure.
W5.185
Modbus inputs in APS enclosure IO
invalid
Possible power supply issue, Ethernet cable fault, Modbus
software malfunction in APS enclosure.
W5.187
24V buffered power supplies not
charged warning
Feedback signal from one of buffer PSU (APS or PE120 enclo-
sure) indicates POWER SUPPLY FAILURE TO CHARGE within a
specified charging period.
W5.189
MCB open or tripped in APS enclo-
sure
One or more MCBs in APS enclosure are OPENED or TRIPPED.
W5.190
Modbus inputs in MVM encl. IO in-
valid
Possible power supply issue, Ethernet cable fault, Modbus
software malfunction in MVM enclosure.
W5.192
APS enclosure temperature high
The APS enclosure temperature is measured as HIGHER THAN
A PRESET LEVEL. This indicates COMPROMISED COOLING.
W5.197
DC insulation resistance low
The resistance of DC conductors is LOWER than the defined
limit.
W5.211
Demand Response Power Controller
communications link invalid
There is a communication problem between the Demand Re-
sponse Power Controller and the MV UPS.
W5.213
Demand Response Power Controller
limiting charging
The Demand Response Controller is LIMITING STATE OF
CHARGE of the Energy Storage.
W5.215
Energy Storage communications link
not valid
There is a communication problem between the Energy Stor-
age and the MV UPS.
—
Table 7.03: List of Warnings and description.