18
13. Accessori
13. Accessories
Sganciatore di apertura (-MO1; -MO2)
Ps
= 125 W/VA (servizio istantaneo < 45 ms)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Sganciatore di chiusura (-MC)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (funzione antipompaggio - servizio continuativo)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Sganciatore di minima tensione (-MU)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (servizio continuativo)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Motoriduttore carica molle (-MS)
Ps
= 1500 W/VA (100 ms)
Pc
= 400 W/VA ( tempo di carica molle 6 s)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Magneti di blocco (-RL1)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (servizio continuativo)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Dispositivo controllo gas con 3 LED
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Dispositivo di visualizzazione interruttore aperto/chiuso
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Dispositivo di visualizzazione molle cariche/scariche
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Contatti ausiliari dell’interruttore
Un
= 500 V~
220 V–
Icu
= 15 A
1,5 A
cos
ϕϕϕϕϕ
= 0,4
–
T
= –
10 ms
Un
Tensione nominale
Cos
ϕϕϕϕϕ
Fattore di potenza
Icu
Potere di interruzione
Ps
Potenza assorbita allo spunto (tra parentesi è
indicata la durata dello spunto)
Pc
Potenza assorbita in servizio continuativo
T
Costante di tempo
13.1. Caratteristiche degli accessori elettrici
Un
Rated voltage
Cos
ϕϕϕϕϕ
Power factor
Icu
Breaking capacity
Ps
Inrush power consumption (the inrush time is
indicated in brackets)
Pc
Continuous service power consumption
T
Time constant
13.1. Characteristics of electrical accessories
Shunt opening release (-MO1; -MO2)
Ps
= 125 W/VA (Instantaneous service < 45 ms)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Shunt closing release (-MC)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (antipumping function - continuous service)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Undervoltage release (-MU)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (continuous service)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Spring charging geared motor ( (-MS)
Ps
= 1500 W/VA (100 ms)
Pc
= 400 W/VA (spring charging time: 6 s)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Locking magnets (-RL1)
Ps
= 250 W/VA (150 ms)
Pc
= 5 W/VA (continuous service)
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Gas control device with 3 LEDs
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Device for showing circuit-breaker open/closed
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Device for showing springs charged/discharged
Un
= 24, 30, 48, 60, 110, 125, 220, 250 V–
Un
= 48, 110, 120 (127), 230 (220/240) V~ 50 Hz
Un
= 110 (127), 230 (220/240) V~ 60 Hz
Circuit-breaker auxiliary contacts
Un
= 500 V~
220 V–
Icu
= 15 A
1,5 A
cos
ϕϕϕϕϕ
= 0,4
–
T
= –
10 ms