Page 36
© Copyright 2021 ABB. All rights reserved.
Programming the Meter
VIM1C parameters like shunt size and number of load buses are preconfigured when it is factory
installed in a BDFB. Only customer specific preferences need to be adjusted in the field. As a
replacement or meter upgrade, the factory default settings may need to be adjusted for the
application. Listed below are the configurable parameters and their associated factory defaults
available through the front panel. Following the table are the typical items that need to be
configured or verified in a retrofit or replacement application.
Table 4 VIM1C Meter Parameters
Item
System
Parameters
Description
1
System Voltage
Factory default is 48V.
2
Local Buzzer
Allows audible alarm to be Enabled or Disabled. Factory default is Disabled.
3
Display Contrast
4
Software Version
Displays the version of the application code running in the meter.
Load Parameters
Description
5
Number Of Loads
Used to identify the number of individual loads/buses in the BDFB. Factory set from 1
-
8 depending
on BDFB configuration.
6
Meter Type
Configures meter to display individual monitored bus voltages (voltage), voltages and currents
(volt_curr), or only currents (current). Factory default is Voltage and Current (volt_curr).
Load ID Format
A, and 1.
“
A1
”
identifies loads using an A1, B1; A2, B2;
…
format.
“
A
”
identifies loads using an A, B,
C, D ... format.
“1”
identifies loads using a 1, 2, 3, 4
…
format. Factor Default is A format.
First Load (location)
top
-
left, top
-
right, btm
-
left (bottom
-
left), btm
-
right (bottom
-
right). Every monitored shunt is
10
Overload Latch
11
Combined Load
Factor default is set to be
“
installed
”.
Load Power Loss
The Power Loss (PL) alarm is triggered upon loss of the primary DC or when the individual
’
s
Summary of Contents for H569-445
Page 6: ...Page 6 Copyright 2021 ABB All rights reserved ...
Page 13: ...Page 13 Copyright 2021 ABB All rights reserved Figure 6 Distribution Connections G7 and G8 ...
Page 22: ...Page 22 Copyright 2021 ABB All rights reserved ...
Page 32: ...Page 32 Copyright 2021 ABB All rights reserved Figure 25 Customer Interface Board ...
Page 34: ...Page 34 Copyright 2021 ABB All rights reserved ...
Page 40: ...Page 40 Copyright 2021 ABB All rights reserved Figure 28 Panel Wiring Schematic G101 and G102 ...
Page 44: ...Page 44 Copyright 2021 ABB All rights reserved ...