34
Installation and maintenance guide
1ZSC000563-AAX EN, REV. A, 2019-03-21
17.
If using a hydraulic jack:
1.
Pull the draw rod with a force according to the table.
2.
Tighten the nut on the draw rod with your hand.
3.
Remove the hydraulic jack.
Type
Force with CT extension 600 mm
GSC 200
37 kN
GSC 300
36.3 kN
GSC 300E
37 kN
GSC 400
37.3 kN
GSC 450S
37.3 kN
GSC 450E
40 kN
GSC 500
40 kN
GSC 500E
40 kN
End of instruction
4.6 Installation of the outer terminal
Procedure
1.
Carefully clean the contact and gasket surfaces
with a soft cloth, and then apply Mobilgrease 28 to
the O-ring (3).
CAUTION!
Do not use a wire brush on the inner
contact surfaces of aluminum outer
terminals.
NOTE!
Or use a lubricant with equal properties
to Mobilgrease 28.
NOTE!
When the outer terminal (5) is installed
at site for grid operation, replace the
used O-ring (3) with a new O-ring. A
new O-ring is supplied with the
bushing.
G006409