Installation
22 - EN
FXE4000 (COPA-XE/MAG-XE)
D184B133U02
3.4.4.4 FXE4000 (MAG-XE), digital communication
Valid for PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, ASCII
G00066
M1
A
Ux
Ux
V8
V8
P7
P7
+VD
FF+
PA+
A
PA-
B
A
FF-
+
B
-
GND
N
L
1+
2-
M2
2
1
3
SE
PE
6
7
8
9
10
11
6
6
6
M1 M2
2
2S
1S
1
3
B
1
2
3
4
5
Fig. 25
1
PROFIBUS PA:
Terminals PA+, PA-:
Connection for PROFIBUS PA according to IEC 61158-2 (Profile
3.0), U = 9 - 32 V, I = 13 mA (normal operation); 17 mA (fault condition / FDE)
2
ASCII-Protocol (RS485):
Terminals Ux, V8:
Scaled pulse output, passive (optocoupler), Pulse width adjustable
between 0.1 ms to 2000 ms,
Optocoupler specifications: f
max
5 kHz, 0 V
≤
U
CEL
≤
2 V, 16 V
≤
U
CEH
≤
30 V,
0 mA
≤
I
CEH
≤
0.2 mA, 2 mA
≤
I
CEL
≤
220 mA
Terminals Ux, P7:
Contact output, function selectable via software e.g. to system monitor,
empty pipe, max. – min. –alarm or V/R contact output
Optocoupler specifications: f
max
5 kHz, 0 V
≤
U
CEL
≤
2 V, 16 V
≤
U
CEH
≤
30 V,
0 mA
≤
I
CEH
≤
0.2 mA, 2 mA
≤
I
CEL
≤
220 mA
Terminals A, B:
Serial data link RS485 for communication using ASCII-Protocol
Ter, -:
Current output, terminals: +/-, current
≤
600
Ω
for 0/4 to 20 mA
3
PROFIBUS DP:
Like design 2 but terVD, A, B, GND connection for PROFIBUS DP according to
EN 50170
4
FOUNDATION Fieldbus:
Terminals FF+, FF-:
Connection for FOUNDATION Fieldbus (H1) according to IEC 61158-
2, U = 9 ... 32 V, I = 13 mA (normal operation); 17 mA (fault condition / FDE)
5
Supply Power:
See name plate
6
Functional ground
7
8
A
White
Blue
Converter
9
10
B
Red
Yellow
Flowmeter primary
11
Steel shielding