Parameters 305
Automatic
The FSO module generates the SLS
acknowledgement signal automatically after
the SLS request has been removed and the
SLS limit has been achieved (that is, SLS
monitoring is on).
Safebus
The FSO module expects an external SLS
acknowledgement signal from the safety
fieldbus. The FSO module accepts the
acknowledgement after the SLS request has
been removed and the SLS limit has been
achieved (that is, SLS monitoring is on).
Manual_Safebus
The FSO module expects an external SLS
acknowledgement signal either from a digital
input or from the safety fieldbus. The FSO
module accepts the acknowledgement after
the SLS request has been removed and the
SLS limit has been achieved (that is, SLS
monitoring is on).
SLSx.03 SLS activation
monitoring method
Sets the monitoring method that is used in
SLS activation.
Ramp
Ramp monitoring. SAR1 parameters define
the deceleration ramp and monitoring limits.
See parameters
Time
Time monitoring. The drive (parameter
23.13
or
23.15)
defines the deceleration ramp and
it is monitored with parameter
.
SLSx.04 SLS time delay
Sets the security delay after which the FSO
module actives the SLS monitoring after the
SLS request.
This parameter is relevant only if time
monitoring is used.
See parameter
Note:
With time monitoring, when
Monitoring active and Modoff delay time is
selected, SLSx.04 and SLSx.06 time must
be set shorter than STO.14, otherwise STO
is not activated due to limit hit when drive
modulation is lost with SLS function.
0 ms
0…4,000,000 ms
Time
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...