Configuration 251
How to configure SSE with ramp monitoring
For more information on the SSE function with ramp monitoring, see page
Example:
The figure below shows an example of the SSE function with ramp
monitoring set-up:
• SAR0 emergency ramp (always with the SSE function)
• SSE with emergency ramp (
=
Emergency ramp
)
• SSE with monitored ramp (
Ramp
). See also
section
on page
.
• redundant emergency stop button connected to input
DI X113:1 & X114:1
)
• single output connected (
= DO X113:9
)
• zero speed limit for activating the drive STO: 90 rpm
90 rpm)
• delay for activating the drive STO after the zero speed limit has been reached:
0 ms (
SSE ramp zero speed delay for STO
=
0 ms
)
• speed limit activated brake not in use
=
0 rpm
).
• See also section
on page
.
Remember to configure SAR0!
Time
Speed
SSE activated
STO activated
Inputs
Outputs
= DI X113:1 & X114:1
= None
= DO X113:9
= None
= Ramp
= Emergency ramp
= Automatic
= 90 rpm
= 0 rpm
= 0 ms
Summary of Contents for FSO-12
Page 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 36: ...36 Safety information and considerations ...
Page 136: ...136 Safety functions ...
Page 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 200: ...200 PROFIsafe ...
Page 326: ...326 Start up ...
Page 386: ...386 Dimension drawings ...