Parameterization
D184B140U02 FSM4000
95
When displaying the operating hours / log time, the ID code combines data record and type
without underscore.
Data record
Type
Numerical
value
Unit
CVC: Current transmitter operating hours counter
H:Min:Sec
-
P1C: Product1-Fingerprint transmitter log time
H:Min:Sec
-
P2C: Product2-Fingerprint transmitter log time
H:Min:Sec
-
DFC: Startup-Fingerprint transmitter log time
H:Min:Sec
-
FVC: Factory Fingerprint transmitter log time
H:Min:Sec
-
H1C – H9C: History 1 – 9 transmitter log time
H:Min:Sec
-
CVP: Current flowmeter sensor operating hours counter
H:Min:Sec
-
P1P: Product1-Fingerprint flowmeter sensor log time
H:Min:Sec
-
P2P: Product2-Fingerprint flowmeter sensor log time
H:Min:Sec
-
DFP: Startup-Fingerprint flowmeter sensor log time
H:Min:Sec
-
FVP: Factory Fingerprint flowmeter sensor log time
H:Min:Sec
-
H1P – H9P: History 1 – 9 flowmeter sensor log time
H:Min:Sec
-
7.4.3.2 Diagnostic warning and error messages
All values acquired during diagnostics or a wiring error can trigger warnings or error messages.
Warnings are displayed in the fourth line only. In the event of an error, the contact output may
as an option (setting "General Alarm" or "ext. Diag. Alarm") be set to alarm state (in addition to
the information displayed in the fourth line).
To activate this option, select in the submenu "Diagnostics / Alert Settings" whether the error or
warning is triggered in the event of over or undershooting the specified range. To check for
wiring errors, you can activate this function under "Diagnostics / Wiring Error".
For additional information, refer to the relevant error registers. These can be selected and
accessed in the Submenus Display or Status.