21/36
6.2.8.2. I1002 Auxiliary-OFF, HW driven Safe–OFF, Delay On/Off, Undervoltage Behaviour
Dip Switch I1002
Auxiliary-tripping
1 2 3
ON
OFF
X
For BI Y3
ON
X
OFF
HW driven Safe–tripping
For BI Y3
ON
OFF
X
Delay for Opening/Closing
Slow Close Toperation = 10ms delay
Slow Trip Toperation = 10ms delay
For BI Y1
For BI Y2 / Y3
ON
X
OFF
Fast Close Toperation = 3ms delay
Fast Trip Toperation = 3ms delay
For BI Y1
For BI Y2 / Y3
ON
OFF
X
Undervoltage Behaviour
CB Blocked in Open position
ON
X
OFF
CB Closing allowed, but then autotripping by the undervoltage function (delay set by DIP I1004)
Table 9
Dip Switches I1004-2/3/4
6.2.8.3. I1004 Delay Time for Undervoltage-Trip
Dip Switch I1004
Delay Time tdelay
1 2 3 4 5
ON
OFF
X X X
Undervoltage-trip function inactive
ON
X
OFF
X X
20 ms
ON
X
OFF
X
X
0.5 s
ON
X X
OFF
X
1 s
ON
X
OFF
X X
2 s
ON
X
X
OFF
X
3 s
ON
X X
OFF
X
4 s
ON
X X X
OFF
5 s
Table 10
Dip Switches I1004-2/3/4
Summary of Contents for FSK II S +