Technical data
Product manual 9AKK107680A3585
│
13
5 Technical
data
5.1 Technical
data
General technical data
Power supply
Gateway operating voltage
100 - 240 V AC
110 - 240 V DC
Voltage range
85 - 265 V AC, 50/60 Hz
110 - 240 V DC
Total power input from the mains
network
*)
6 W max.
Total power consumption from the
mains network
*)
Max. 25 mA
Total power loss of device
*)
2 W max.
Power consumption of
free@home
Max. 10 mA
Power consumption via
free@home
max. 210 mW
*) at 230 V AC and max. load
DALI outputs (channels)
Number of outputs
1
Voltage-proof, short-circuit-proof
230 V AC
Number of DALI operating
equipment
Maximum of 16 per output
Distance of gateway to the last
DALI device for cable cross
section
■
0.5 mm²
■
0.75 mm²
■
1.0 mm²
■
1.5 mm²
100 m
1)
150 m
1)
200 m
1)
300 m
1)
Connectors
free@home
free@home connecting terminal,
0.8 mm Ø, single-wire
DALI outputs and mains voltage
Screw-type terminal, combi-
head
0.5 - 4 mm²
fine-wire
0.5 - 4 mm²,
single-wire
Tightening torque
Max. 0.6 Nm
Protection rating
IP 20
According to DIN EN 60 529
Protection class
II
According to DIN EN 61 140
Insulation category
Overvoltage category
III according to DIN EN 60 664-1
Pollution degree
2 according to DIN EN 60 664-1
Safety Extra Low Voltage
SELV 24 V DC
DALI voltage
Typical 16 V DC
(12 - 20.5 V DC)
According to DIN EN 60 929
and IEC 62 386
No-load voltage
18 VDC
Smallest supply current at 12 V
DC
160 mA