Start-up
To control the drive with the adapter module, set at least the basic parameters listed in the table
below. For full parameter descriptions, refer to the adapter module’s user manual or to the drive’s
firmware manual.
Basic parameter settings
To take the settings into use, validate and refresh the parameters with parameter
51.27 FBA par
refresh
.
Connectivity configuration
The FEIP-21 adapter module has a web page for connectivity configuration.
To access the web page:
1.
Open a web browser and type the IP address of the adapter module in the address field.
The IP address is visible in group 51, parameters 5...8
Example
: https://192.168.0.24/
2.
Log in with a user name and a password.
The default user name: admin
Password: The last six digits of the MAC address of the adapter module, in upper case letters,
without hyphens. The MAC address is visible on the front cover of the adapter module.
Example
: If the MAC address of the adapter module is 00-1C-01-00-2F-73, the password is
002F73
.
Further information
Index
Name
Value
20.01
Ext1 commands
Fieldbus A
22.11
Speed ref1 source
FBA A ref 1
28.11
Frequency ref1 source
FBA A ref 1
50.01
FBA A enable
Enable (or select the option slot in which the module is installed). This activates the
communication module. The HOST LED becomes green.
50.02
FBA A comm loss func
Fault
51.02
Profile
The ODVA AC/DC drive profile (EIP AC/DC) is the default value.
51.04
IP configuration
Set the IP address according your network configuration.
51.05...08
IP address
51.09
Subnet CIDR
See the latest version of
FEIP-21 Ethernet/IP adapter module
user's manual (3AXD50000158621 [English])
in ABB library
).
For more information on ABB fieldbus options and protocols,
see the fieldbus communications web page