22
22
LED state
Description
Off
The auxiliary power supply voltage is disconnected
On
Normal functionality
Flashing
There has been an internal fault or the IED is in the test mode. Internal faults are accompanied by an error message.
Ready Led
LED state
Description
Off
Normal functionality
On
One of the protection functions is above threshold, a notification message is displayed at the same time.
– If various protections are above threshold within a short time interval, notification regarding the last function which has
passed into the first threshold is shown.
Flashing
One of the functions is blocked.
– The blocked indication disappears when the block is removed or when the function is reset.
Start Led
LED state
Description
Off
Normal functionality
On
One of the protection functions has tripped, a notification message is displayed at the same time.
– The trip indication remains on and must be reset by means of the communication or by means of the Clear button
.
Trip Led
5.3.7.16. LEDs
The LHMI includes three LEDs for indicating the state of the protections and of the relay functions. A further 8 alarm LEDs are
available on the front of the LHMI. By means of these 8 LEDs it is possible to display the state of 24 alarms organized into three
pages. The “Alarm page” button allows switching among the various LED pages. These LEDs can be configured by means of
PCM600.
LHMI functions
Protection and alarm indications. There are three LEDs which indicate the state of the protections: Ready, Start and Trip.
5.3.7.17. Parameter management
The LHMI allows the IED parameters to be accessed. Three
types of parameters can be read or written:
– Numerical values
– Strings
– Enumeration
The numerical values are presented both in full and decimal
form with one minimum and one maximum value. The string
parameters can be entered character by character. The
enumerated parameters have a set of pre-established values
within which they can vary.
5.3.7.18. Front communication port
The RJ45 type communication port allows connection to the
RBX615 relay.
When a computer is connected with the IED, the DHCP server
of the IED for the front port assigns an IP address to the
computer. The IP address of the front port is fixed and is
192.168.0.254