116 The ESI-Manager user interface
Manual Energy Storage Inverter ESI-S
For commissioning the inverter follow the commissioning procedure presented in
Remarks:
−
The commissioning window incorporates the start, stop and fault
acknowledgement menu (Cf.
Section 7.7
−
For advanced inverter setup (auto restart function, standby function, system
clock setup, external communication setup, system lock activation and password
setup) refer to
Section 7.9.4
.
7.9.3.1 Setting up the network characteristics and the inverter synchro mode
For modifying the network characteristics and the inverter synchro mode, go to
[/Welcome/Settings/Commissioning/Network charact.]
The network characteristics include:
−
The nominal supply voltage: This value has to be set up according to the nominal
value of the grid voltage.
WARNING: For ESI-S inverter, the hardware is by default set for operation at voltages
in the range 380-415V. When the inverter is used in networks with voltages in the range
208-240V, its hardware configuration needs to be changed. Refer to
Section 6.7.
for
guidelines on how this needs to be done. Failure to adapt the inverter hardware to the
right network voltage range may result in hardware failure.
−
The nominal value of the network frequency: This value has to be set up according
to the nominal value of the network frequency.