Manual Energy Storage Inverter ESI-S
The ESI-Manager user interface 91
−
Most setting values can be consulted
Once the ESI-Manager is locked, it can be unlocked by pushing the blue button again.
In order to prevent unauthorized modification of the core installation settings of the
active inverter but still giving them access to typical user settings (e.g. harmonics
selection, programming digital outputs, …), switch on the software lock.
The communication lock is applied when the corresponding parameter is set through
the menu interface. When the lock is set:
−
will appear when the settings can be changed only through the communication
The software lock is applied when the corresponding parameter is set through the menu
interface. When the lock is set:
−
will appear. No modification can be made to the settings
The software lock is switched on in the menu [/Welcome/Settings/Installation
set./Password].
In order to unlock the system go to the same menu. After giving the appropriate
password, the system will be unlocked. The password is a four-digit number, which is
set by default to:
1234
Entering the password is done by choosing the right value numeric keyboard which
appears on the screen. The password can be changed in the menu
[/Welcome/Settings/Installation set/Change Password]. Entering the new password is
done the same way and confirming the password by re-entering the same.
If hardware and software lock are combined, the hardware lock has priority over the
software lock.
Note: In active inverter systems consisting of more than one master, the ESI-Manager of
the master that has the control over the system has full functionality and the ESI-
Managers of the other master units have limited functionality. The hardware lock in the
master has no effect on access level of parameters in the slave modules like warning
(alarm …). To disable these settings the hardware lock of each ESI-Manager must be
engaged.
7.7 The ESI start, stop and fault acknowledgement menu
WARNING: The active inverter should only be started when it has been installed and
commissioned according to the guidelines of this manual. Failure to adhere to this
guideline may damage the inverter and void warranty.
Refer to
for more information on commissioning the inverter.