ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
47
No.
Function
Object name
Data type
Flags
21
Status control value
1 byte
Output A
1 byte
DPT 5.001
C, R, T
This communication object is enabled in parameter window
A: Functions
, page 32, via pa-
rameter
Enable communication object "Status control value"
with the option
1 byte
.
The control status of the output is sent via this communication object. Hereby, the limit posi-
tion that the valve should assume is transferred.
The LED of the corresponding output indicates the same value as the status.
The status is sent if
- a request is received via the communication object
Request status values
and
the
parameter
after request
or
after a change or request
is present.
- the value of the communication object has changed and the parameter
after a change
or
after change or request
is present.
- a read request is carried out on this communication object.
Telegram value:
0…255 = control value is displayed directly as a figure value
at 0 = LED (yellow) off
at > 0 = LED (yellow) on
If in parameter window
General
under parameter
Control value is received as
the option
1 bit
is selected, the following applies for the communication object
Status control value 1 byte
:
Telegram value:
0
= control value 0; control equal to zero; LED (yellow) off
255
= control value 1; control not equal to zero; LED (yellow)
on
21
Status control value
1 bit
Output A
1 bit
DPT 1.011
C, R, T
This communication object is enabled in parameter window
A: Functions
, page 32, via pa-
rameter
Enable communication object "Status control value"
with the option bit.
The control status of the output is sent via this communication object. Hereby, the limit posi-
tion that the valve should assume is transferred.
The LEDs of the corresponding outputs indicate the same value as the status.
The status is sent if
- a request is received via the communication object
Request status values
and
the
parameter
after request
or
after a change or request
is present.
- the value of the communication object has changed and the parameter
after a change
or
after change or request
is present.
- a read request is carried out on this communication object.
Telegram value:
0 = control equal to zero; LED (yellow) off
1 = control not equal to zero; LED (yellow) on
22…
25
Not assigned.