ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
43
3.3.3 Communication
objects
Output A
Operation mode Valve
drive (thermoelectric)
Note
However, as the functions for all outputs are identical, only the functions
of output A will be described.
No.
Function
Object name
Data type
Flags
10
Control value, switch 1 bit
Output A
1 bit
DPT 1.001
C, W
This communication object is always displayed. Using the parameter
Control will be received
as
in parameter window
A: General
,
page 26, control can toggle between 1 bit and 1 byte
control.
1 bit: The ES/S receives the ON or OFF telegrams from the thermostat.
Telegram value
0 = OFF
1 = ON
10 Control
value,
continuous
(PWM) 1 byte
Output A
1 byte
DPT 5.001
C, W
This communication object is always displayed. Using the parameter
Control will be received
as
in parameter window
A: General
,
page 26, control can toggle between 1 bit and 1 byte
control.
1 byte: The communication object value [0…255] determines the variable mark-to-space
ratio of the valve drive. The output switches OFF with communication object value 0
(valve drive closes); at communication object value 255, the output switches continuously
ON (valve drive opens completely).
Telegram value
0 = OFF (valve drive closed)
x = intermediate values
255 = ON (valve drive opened)