Wiring the secondary disconnects and verifying they match the switchgear cublicle may take
1 to 8 hrs depending on the complexity of the original breaker. Once the retrofill breaker is
fully prepared, it should take about 20 minutes to swap out the old breaker and rack in the
new Emax 2 Retrofill circuit breaker if the proper lifting bar and hoist are available, it may take
an additional 30 min to replace the door.
The Emax 2 Retrofill, when ordered with 4 wire ground fault, will be equipped with a Neutral
CT adapter. The adapter will modify the GE MicroVersa Trip type Neutral CT output to a
Rogowski sensor output compatible with the Emax 2 Retrofill Trip Unit. With this device, it
will not be necessary to change the neutral CT in the switchgear to a Rogowski sensor. If the
trip unit types used are CS, SST or PS-1 POWER SENSOR™, then the CT should be replaced
with the Microversa Trip type.
6 ©2022 Emax 2 Retrofill Circuit Breakers 800A-4000A
2TSA451014P0000 Rev-B
Installation Manual AKD 10
Installation Manual AKD 8
Installation Manual AKD 6
Installation Manual AKD 5
Accessory: Door Interlock (Door Interlock Kit)
Accessory: Kirk Key Installation Manual
Accessory: Retrofill Direct Replacement / CiC Full Door Kits AKD-5, 6, 8 & 10
Accessory: Retrofill Direct Replacement / CiC Adaptors Kits AKD-5, 6, 8 & 10
Accessory: OEM Direct Replacement Adaptor kits AKD-8 & 10
Accessory OEM Direct Replacement Adaptor kits, AKD8 &10, AKR 75/100, B&F TYPE
Accessory OEM Direct Replacement Adaptor kits, AKD8 & 10, only for AKR30S
Accessory: Position Switch Plate, Assembly & Wiring
Accessory: Neutral CT Adapters Installation Instructions
Accessory: Programmer Disconnects Installation Instructions
Accessory: Primary Disconnects Installation Instructions
Accessory: Secondary Disconnects, Installation Instructions
E2.2, 4.2, 6.2 Breakers Installation, Operation & Maintenance Manual
Instructions for using Ekip touch protection releases & accesories
Emax 2 Family Trip units Engineering manual
2TSA451010P0000
2TSA451009P0000
2TSA451014P0000
2TSA451011P0000
2TSA451017P0000
2TSA451013P0000
2TSA451007P0000
2TSA451008P0000
2TSE431967R1000
2TSE431968R1000
2TSE431996R1000
2TSA451019P0000
2TSA451018P0000
2TSA451012P0000
2TSA451015P0000
2TSA451016P0000
1SDH001000R0002
1SDH001316R0002
1SDH001330R0002
Publication
Publication Number