IEC 60870-5-101 and IEC 60870-5-104
Functions
Type ids IEC-101 / IEC-104
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec104
convert
types
(Stan-
dard)
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec101
convert
no asdu-
types
22-29
TYPE_22-29
Reserved (standard range)
22-29
22-29
30
M_SP_TB_1
Single message with time
stamp CP56Time2a
30
30
31
M_DP_TB_1
Double message with time
stamp CP56Time2a
31
31
32
M_ST_TB_1
Level setting message with
time stamp CP56Time2a
32
32
33
M_BO_TB_1
Bit pattern 32 bit with time
stamp CP56Time2a
33
33
34
M_ME_TD_1
Measured value, standard-
ized value with time stamp
CP56Time2a
34
34
35
M_ME_TE_1
Measured value, scaled
value with time stamp
CP56Time2a
35
35
36
M_ME_TF_1
Measured value, floating
point with single accu-
racy and time stamp CP56-
Time2a
36
36
37
M_IT_TB_1
Counted values with time
stamp CP56Time2a
37
37
38
M_EP_TD_1
Protection event with time
stamp CP56Time2a
38
38
39
M_EP_TE_1
Blocked stimulations of the
protection with time stamp
CP56Time2a
39
39
40
M_EP_TF_1
Blocked triggers of the pro-
tection with time stamp
CP56Time2a
40
40
41-44
TYPE_41-44
Reserved (standard range)
41-44
41-44
45
C_SC_NA_1
Single command
58
45
46
C_DC_NA_1
Double command
59
46
47
C_RC_NA_1
Level setting command
60
47
48
C_SE_NA_1
Target value setting com-
mand, standardized value
61
48
Table 36: Type conversion in message direction
82
1KGT151021
V000 1