Functions
IEC 60870-5-101 and IEC 60870-5-104
Type ids IEC-101 / IEC-104
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec104
convert
types
(Stan-
dard)
Message
direc-
tion /
Monitor
direction
Conver-
sion to
IEC-104
type id
iec101
convert
no asdu-
types
5
M_ST_NA_1
Level setting message
5
5
6
M_ST_TA_1
Level setting message with
time stamp CP24Time2a
32
6
7
M_BO_NA_1
Bit pattern 32 bit
7
7
8
M_BO_TA_1
Bit pattern 32 bit with time
stamp CP24Time2a
33
8
9
M_ME_NA_1
Measured value, standard-
ized value
9
9
10
M_ME_TA_1
M_ME_TA_1 Measured value,
standardized value with time
stamp CP24Time2a
34
10
11
M_ME_NB_1
Measured value, scaled value 11
11
12
M_ME_TB_1
Measured value, scaled
value with time stamp
CP24Time2a
35
12
13
M_ME_NC_1
Measured value, floating
point with single accuracy
13
13
14
M_ME_TC_1
Measured value, floating
point with single accu-
racy and time stamp CP24-
Time2a
36
14
15
M_IT_NA_1
Counted values
15
15
16
M_IT_TA_1
Counted values with time
stamp CP24Time2a
37
16
17
M_EP_TA_1
Protection event with time
stamp CP24Time2a
38
17
18
M_EP_TB_1
Blocked stimulations of the
protection with time stamp
CP24Time2a
39
18
19
M_EP_TC_1
Blocked triggers of the pro-
tection with time stamp
CP24Time2a
40
19
20
M_PS_NA_1
Packed single messages with
status indicator
20
20
21
M_ME_ND_1
Measured value, standard-
ized value without quality id
21
21
Table 36: Type conversion in message direction