54
ACH550-UH User’s Manual
0118
DI1-3 STATUS
000…111
1
-
(0…7 decimal)
Status of the three digital inputs.
• Status is displayed as a binary number.
• 1 indicates that the input is activated.
• 0 indicates that the input is deactivated.
0119
DI4-6 STATUS
000…111
1
-
(0…7 decimal)
Status of the three digital inputs.
• See parameter 0118
DI
1-3
STATUS
.
0120
AI1 0…100%
0.1%
-
Relative value of analog input 1 in %.
0121
AI2 0…100%
0.1%
-
The relative value of analog input 2 in %.
0122
RO1-3 STATUS
0…111
1
-
(0…7 decimal)
Status of the three relay outputs.
• 1 indicates that the relay is energized.
• 0 indicates that the relay is de-energized.
0123
RO4-6 STATUS
0…111
1
-
(0…7decimal)
Status of the three relay outputs. See parameter 0122.
0124
AO1 0…20
mA
0.1
mA
-
The analog output 1 value in milliamperes.
0125
AO2 0…20
mA
0.1
mA
-
The analog output 2 value in milliamperes.
0126
PID 1 OUTPPUT
-1000…1000%
0.1%
-
The PID Controller 1 output value in %.
0127
PID 2 OUTPUT
-100…100%
0.1%
-
The PID Controller 2 output value in %.
0128
PID 1 SETPNT
-
-
-
The
PID
1 controller setpoint signal.
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
0129
PID 2 SETPNT
-
-
-
The
PID
2 controller setpoint signal.
• Units and scale defined by PID parameters 4206 & 4207.
0130
PID 1 FBK
-
-
-
The
PID
1 controller feedback signal.
• Units and scale defined by PID parameters 4006/4106 & 4007/4107.
Group 01: Operating Data
Code
Description Range
Resolution
Default
S
DI
1
DI
2
DI
3
RELAY
1
STATUS
RELAY
2
STATUS
RELAY
3
STATUS