ACH550-UH User’s Manual
17
Installation
Wiring IP 54 / UL Type 12 Enclosure
1. Step depends on Frame Size:
•
Frame Sizes R1…R4: Remove and
discard the cable seals where conduit will
be installed. (The cable seals are cone-
shaped, rubber seals on the bottom of the
drive.)
•
Frame Sizes R4 and R5: Use punch to
create holes for conduit connections as
needed.
2. For each conduit run (input power, motor and
control wiring must be separate), install water
tight conduit connectors (not supplied).
3. Route the power wiring through conduit.
4. Route the motor wiring through conduit (not
the same conduit as input power wiring run).
5. Strip the wires.
6. Connect the power, motor, and ground wires
to the drive terminals. See "Wiring Overview"
on page 13, and "Connection Diagrams" on
page 14.
7. Route the control cables through the conduit
(not the same conduit as either input power or
motor wiring runs).
8. Strip the control cable sheathing and twist the
copper screen into a pig-tail.
9. Connect the ground screen pig-tail for digital
and analog I/O cables at X1-1. (Ground only
at drive end.)
10. Connect the ground screen pig-tail for RS485
cables at X1-28 or X1-32. (Ground only at
drive end.)
11. Strip and connect the individual control wires
to the drive terminals. See "Wiring Overview"
on page 13.
12. Install the conduit box cover (1 screw).
IP5013
1
IP5023
1
2
IP5006
3
IP5007
6
4
7
IP5008
9…11